7
A
For installation in the switch box:
B
For direct installation on the wall select one of the following:
• Prepare a hole through the wall to pass the remote controller cord (in order to run the remote controller cord from
the back), then seal the hole with putty.
• Run the remote controller cord through the cut-out upper case, then seal the cut-out notch with putty similarly as
above.
C
Wall
D
Conduit
E
Lock nut
F
Bushing
G
Switch box
H
Remote controller cord
I
Seal with putty
J
Wood screw
F
A
H
C
D
E
G
I
I
I
H
B
J
H
B-1.
B-2.
[Fig. 8-5]
8
A
AB
TB6
B
A
To the terminal block on the indoor unit
B
TB6 (No polarity)
[Fig. 8-6]
8.2
30
46
30
30
120
83.5
A
B
C
A
Remote controller profile
B
Required clearances surrounding the remote controller
C
Installation pitch
[Fig. 8-4]
[Fig. 8-3]
A
Indoor terminal block
B
Earth wire (green/yellow)
C
Indoor/outdoor unit connecting wire 3-
core 1.5 mm
2
or more
D
Outdoor terminal block
E
Power supply cord : 2.0 mm
2
or more
1
Connecting cable
Cable 3-core 1.5 mm
2
, in conformity
with Design 245 IEC 57.
2
Indoor terminal block
3
Outdoor terminal block
A
Indoor terminal block
4
Always install an earth wire (1-core 1.5 mm
2
)
longer than other cables
5
Remote controller cable
Wire No
×
size (mm
2
) : Cable 2C
×
0.3
This wire accessory of remote controller
(wire length : 10m, non-polar. Max. 500m)
6
Wired remote controller (option)
7
Power supply cord
Cable 3-core 2.0 mm
2
or more, in conform-
ity with Design 245 IEC 57.
1 2
6
5
2
4
3
7
L N
1
C
Indoor/outdoor unit
connecting wire
3-core 1.5 mm
2
or
more
D
Outdoor terminal block
B
Earth wire (green/yellow)
E
Power supply cord : 2.0 mm
2
or more
8.3
00b_KB79U749H01_Illust.p65
10.10.14, 9:13
7