background image

22

9.1. Before test run

After completing installation and the wiring and piping of the indoor and outdoor
units, check for refrigerant leakage, looseness in the power supply or control
wiring, wrong polarity, and no disconnection of one phase in the supply.
Use a 500-volt megohmmeter to check that the resistance between the power
supply terminals and ground is at least 1.0 M

.

Do not carry out this test on the control wiring (low voltage circuit) termi-
nals.
 Warning:

Do not use the air conditioner if the insulation resistance is less than 1.0 M

.

Insulation resistance

After installation or after the power source to the unit has been cut for an extended
period, the insulation resistance will drop below 1 M

 due to refrigerant accumulat-

ing in the compressor. This is not a malfunction. Perform the following procedures.
1. Remove the wires from the compressor and measure the insulation resistance of

the compressor.

2. If the insulation resistance is below 1 M

, the compressor is faulty or the resist-

ance dropped due the accumulation of refrigerant in the compressor.

3. After connecting the wires to the compressor, the compressor will start to warm

up after power is supplied. After supplying power for the times indicated below,
measure the insulation resistance again.

The insulation resistance drops due to accumulation of refrigerant in the com-
pressor. The resistance will rise above 1 M

 after the compressor is warmed

up for two to three hours.
(The time necessary to warm up the compressor varies according to atmos-
pheric conditions and refrigerant accumulation.)

To operate the compressor with refrigerant accumulated in the compressor,
the compressor must be warmed up at least 12 hours to prevent breakdown.

4. If the insulation resistance rises above 1 M

, the compressor is not faulty.

 Caution:

• The compressor will not operate unless the power supply phase connection

is correct.

• Turn on the power at least 12 hours before starting operation.

- Starting operation immediately after turning on the main power switch can result in

severe damage to internal parts. Keep the power switch turned on during the op-
erational season.

9. Test run

9.2. Test run

9.2.1. Using wired remote controller (option)

1

Turn on the power at least 12 hours before the test run.

2

Press the [TEST] button twice. 

 “TEST RUN” liquid crystal display

3

Press the [Mode selection] button. 

 Make sure that wind is blown out.

4

Press the [Mode selection] button and switch to the cooling (or heating) mode.

 Make sure that cold (or warm) wind is blown out.

5

Press the [Fan speed] button. 

 Make sure that the wind speed is switched.

6

Check operation of the outdoor unit fan.

7

Release test run by pressing the [ON/OFF] button. 

 Stop

8

Register a telephone number.
The telephone number of the repair shop, sales office, etc., to contact if an error
occurs can be registered in the remote controller. The telephone number will be
displayed when an error occurs. For registration procedures, refer to the operation
manual for the indoor unit.

[Fig. 9-1] (P.11)

A

ON/OFF button

B

Test run display

C

Indoor temperature liquid line temperature display

D

ON/OFF lamp

E

Power display

F

Error code display

Test run remaining time display

G

Set temperature button

H

Mode selection button

I

Fan speed button

M

TEST button

9.2.2. Wired remote controller

1

Turn on the power.

2

Press the [CHECK] button twice.

3

Set refrigerant address with [TEMP] button if system control is used.

4

Press the [ON/OFF] button to stop the self-check.

[Fig. 9-2] (P.11)

A

CHECK button

B

Refrigerant address

C

TEMP. button

D

IC:

Indoor unit

OC: Outdoor unit

E

Check code

• For description of each check code, refer to the following table.

1

 Check code

Symptom

Remark

P1

Intake sensor error

P2, P9

Pipe (Liquid or 2-phase pipe) sensor error

E6, E7

Indoor/outdoor unit communication error

P4

Drain sensor error

P5

Drain pump error

PA

Forced compressor error

P6

Freezing/Overheating safeguard operation

EE

Communication error between indoor and outdoor units

P8

Pipe temperature error

E4

Remote controller signal receiving error

Fb

Indoor unit control system error (memory error, etc.)

E0, E3

Remote controller transmission error

E1, E2

Remote controller control board error

E9

Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)

UP

Compressor overcurrent interruption

U3, U4

Open/short of outdoor unit thermistors

UF

Compressor overcurrent interruption (When compressor locked)

U2

Abnormal high discharging temperature/49C worked/insufficient refrigerant

U1, Ud

Abnormal high pressure (63H worked)/Overheating safeguard operation

U5

Abnormal temperature of heat sink

U8

Outdoor unit fan safeguard stop

U6

Compressor overcurrent interruption/Abnormal of power module

U7

Abnormality of super heat due to low discharge temperature

U9, UH

Abnormality such as overvoltage or voltage shortage and abnormal synchronous signal to main circuit/
Current sensor error

Others

Other errors (Refer to the technical manual for the outdoor unit.)

• On wired remote controller

1

Check code displayed in the LCD.

For details, check the LED display
of the outdoor controller board.

01_KB79U749H01_GB.p65

2011.10.26, 4:49 PM

22

Содержание Mr.Slim PEAD-RP100JAA

Страница 1: ...INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit Air Conditioners PEAD RP71 100 125 140JAA English FOR INSTALLER ...

Страница 2: ...e viewed from the side G Service space viewed from the direction of arrow 1 600 mm or more 2 100 mm or more 3 10 mm or more 4 300 mm or more Y X L W A Z C Nuts field supply D Washers accessory E M10 hanging bolt field supply B C D A F G 3 4 E A 50 150 450 450 57 643 777 30 98 23 C B A D B E 250 1 2 B A Model PEAD RP71 PEAD RP100 125 PEAD RP140 A 1100 1400 1600 B 1154 1454 1654 C 1200 1500 1700 D 1...

Страница 3: ...sory H Thermal insulation field supply I Pull J Flare nut K Return to original position A B C D F G E H H K L J I J O O N N 20 20 20 20 Fig 6 3 Fig 6 6 Fig 6 4 Fig 6 5 a Flare nut b Copper tube a Burr b Copper tube pipe c Spare reamer d Pipe cutter Fig 6 7 Fig 6 8 a Flaring tool b Die c Copper tube d Flare nut e Yoke a Smooth all around b Inside is shining without any scratches c Even length all a...

Страница 4: ...ixing part D Insertion margin E Drain socket accessory F Drain pipe O D ø32 PVC TUBE field supply G Insulating material field supply A B 1 C C C D 2 E A Downward slope 1 100 or more B Connection dia R1 external thread C Indoor unit D Collective piping E Maximize this length to approx 10 cm ...

Страница 5: ...oor unit outdoor unit connecting cords F Remote controller option G Indoor unit H Option J Indoor unit power supply S1 S2 L N 1 2 L N S1 S2 S3 S3 A C B D J E B C F G H A Outdoor unit power supply B Earth leakage breaker C Wiring circuit breaker or isolating switch D Outdoor unit E Indoor unit outdoor unit connecting cords F Remote controller option G Indoor unit H Option J Indoor unit power supply...

Страница 6: ...e a cable tie to secure the cable G Power source wiring H Use ordinary bushing I Transmission wiring J Terminal block for power source and indoor transmission K Terminal block for remote controller Fig 8 2 3 Fig 8 2 4 C Terminal box D Knockout hole E Remove A Screw holding cover 1pc B Cover Fig 8 2 1 Fig 8 2 2 8 A B C D E H I F G J K ...

Страница 7: ...es surrounding the remote controller C Installation pitch Fig 8 4 Fig 8 3 A Indoor terminal block B Earth wire green yellow C Indoor outdoor unit connecting wire 3 core 1 5 mm2 or more D Outdoor terminal block E Power supply cord 2 0 mm2 or more 1 Connecting cable Cable 3 core 1 5 mm2 in conformity with Design 245 IEC 57 2 Indoor terminal block 3 Outdoor terminal block A Indoor terminal block 4 Al...

Страница 8: ...10 A B C A Fix tightly with tape B Remote controller wire C Order wire Indoor unit Fig 8 8 Fig 8 11 H J I When using the switch box When installing directly on the wall A 150 mm 5 15 16 inch B Remote controller wire C Wiring pipe D Locknut H Seal around here with putty I Remote controller wire J Seal around here with putty E Bushing F Switch box G Seal around here with putty C D B F E G A Wall 8 8...

Страница 9: ...r case directly on the wall or the ceiling use wood screws Insert the minus screwdriver toward the arrow pointed and wrench it to remove the cover A flat screwdriver whose width of blade is between 4 and 7mm 5 32 9 32inch must be used Fig 8 15 1 1 2 A 1 Hang the cover to the upper hooks 2 places 2 Mount the cover to the lower case A Cross section of upper hooks ...

Страница 10: ...air number 1 Pair number 2 Pair number 3 Pair number 0 Pair number 1 Pair number 2 Pair number 3 Pair number 0 Pair number 0 Pair number 0 Pair number 0 A CN2A CN3C SW2 SW1 JP1 JP2 JP3 JP41 JP42 CN22 CN2L CNXA2 CN32 SWE CN20 CN90 CN105 CN41 CN4F CN51 CNXB2 CNXC2 CN44 ON OFF Indoor controller board ON OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOUVER MODE CHECK RESET SET CLOCK CHECK 2 4 ...

Страница 11: ...M TEST button 8 8 5 Fig 8 21 PAR 21MAA ON OFF FILTER CHECK OPERATION CLEAR TEST TEMP MENU BACK DAY MONITOR SET CLOCK ON OFF A B D C G E F 4 1 2 1 3 4 1 2 A Filter button Enter button B TEST button C Set Time button D Timer On Off button Set Day button E Mode selection button F Set temperature button G Timer Menu button Monitor Set button Mode number Setting number Refrigerant address Unit number 1...

Страница 12: ...pe D Gas pipe E Stop valve F Outdoor unit G Refrigerant gas cylinder operating valve H Refrigerant gas cylinder for R410A with siphon I Refrigerant liquid J Electronic scale for refrigerant charging K Charge hose for R410A L Gauge manifold valve for R410A M Service port 10 1 ...

Страница 13: ...pply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard Attach the electrical part cover to the indoor unit and the service panel to the outdoor unit securely If the electrical part cover in the indoor unit and or the service panel in the outdoor unit are not attached securely it could result in a fire or an electric ...

Страница 14: ...to the configuration of the room and the installation position As the piping and wiring are connected at the bottom and side surfaces and the maintenance is made at the same surfaces allow a proper space properly For the efficient suspension work and safety provide a space as much as possible 3 3 Indoor unit accessories The unit is provided with the following accessories No Name Quantity 1 Pipe co...

Страница 15: ...ed copper piping C Liquid end of refrigerant piping D Gas end of refrigerant piping E Site refrigerant piping F Main body G Pipe cover large accessory H Thermal insulation field supply I Pull J Flare nut K Return to original position L Ensure that there is no gap here M Plate on main body N Band accessory O Ensure that there is no gap here Place join upwards Pipe For liquid For gas For liquid For ...

Страница 16: ...pe This metal brace should be provided 50 cm away from the indoor unit s flare connection Close Open Hexagonal wrench Stop valve 4 to 5 turns Stop valve or the vacuum pump with the function to prevent the back flow Gauge manifold valve for R410A Pressure gauge for R410A Compound pressure gauge for R410A 0 101MPa 760 mmHg Handle Low Handle High Window Charge hose for R410A Vacuum pump Adapter for p...

Страница 17: ... inlet Caution Inlet duct of 850 mm or more should be construted To connect the air conditioner main body and the duct for potential equali zation To reduce the risk of injury from metal sheet edges wear protective gloves To connect the air conditioner main body and the duct for potential equali zation The noise from the intake will increase dramatically if intake is fitted di rectly beneath the m...

Страница 18: ...win triple four system The optional wiring replacement kits are required Fig 8 4 P 5 A Outdoor unit power supply B Earth leakage breaker C Wiring circuit breaker or isolating switch D Outdoor unit E Indoor unit outdoor unit connecting cords F Remote controller option G Indoor unit H Option J Indoor unit power supply Affix a label B that is included with the manuals near each wiring diagram for the...

Страница 19: ...wn in Fig 8 3 P 7 Caution Use care not to make mis wiring Firmly tighten the terminal screws to prevent them from loosening After tightening pull the wires lightly to confirm that they do not move 8 3 Remote controller wired remote controller option 8 3 1 For wired remote controller 1 Installing procedures 1 Select an installing position for the remote controller The temperature sensors are locate...

Страница 20: ...ing the wire out of the back of the Signal Receiving Unit seal that hole with putty When routing the wire via the portion cut off from the upper case equally seal that portion with putty 4 Install the remote control wire to the terminal block Fig 8 12 P 9 5 Installing hole when the Signal Receiving Unit is installed on the wall direct Fig 8 13 P 9 Cut the thin wall portion inside the bottom case o...

Страница 21: ...t operating average Set by indoor unit s remote controller Remote controller s internal sensor Not Supported Supported indoor unit is not equipped with outdoor air intake Supported indoor unit is equipped with outdoor air intake 240V 220V 230V Energy saving cycle automatically enabled Energy saving cycle automatically disabled Mode no Setting no Initial setting Check 1 1 01 2 1 02 2 3 1 03 2 3 1 0...

Страница 22: ...tton and switch to the cooling or heating mode Make sure that cold or warm wind is blown out 5 Press the Fan speed button Make sure that the wind speed is switched 6 Check operation of the outdoor unit fan 7 Release test run by pressing the ON OFF button Stop 8 Register a telephone number The telephone number of the repair shop sales office etc to contact if an error occurs can be registered in th...

Страница 23: ...it Remark For details check the LED display of the outdoor controller board Output pattern A Errors detected by indoor unit Wireless remote controller Beeper sounds OPERATION INDICATOR lamp flashes Number of times 1 2 3 4 5 6 7 8 9 10 11 12 No sound Wired remote controller Check code P1 P2 P9 E6 E7 P4 P5 P6 EE P8 E4 Fb Symptom Intake sensor error Pipe Liquid or 2 phase pipe sensor error Indoor out...

Страница 24: ...To maintain the high pressure of the gas cylinder warm the gas cylinder with warm water under 40 C during cold season But never use naked fire or steam 9 Test run Indicates whether control power is supplied Make sure that this LED is always lit Indicates whether power is supplied to the remote controller This LED lights only in the case of the indoor unit which is connected to the outdoor unit ref...

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ...KD79D905H02 Please be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Отзывы: