1. Safety precautions

s

Before installing the unit, make sure you read all the “Safety precau-
tions”.

s

Please report to or take consent by the supply authority before connec-
tion to the system.

 Warning:

Describes precautions that must be observed to prevent danger of injury or
death to the user.

 Caution:

Describes precautions that must be observed to prevent damage to the unit.

After installation work has been completed, explain the “Safety Precautions,” use,
and maintenance of the unit to the customer according to the information in the Op-
eration Manual and perform the test run to ensure normal operation. Both the Instal-
lation Manual and Operation Manual must be given to the user for keeping. These
manuals must be passed on to subsequent users.

: Indicates a part which must be grounded.

 Warning:

Carefully read the labels affixed to the main unit.

Contents

1. Safety precautions ................................................................................... 2
2. Installation location .................................................................................. 3
3. Installing the indoor unit ........................................................................... 3
4. Installing the refrigerant piping ................................................................. 5
5. Drainage piping work (Fig. 5-1) ................................................................ 6

6. Electrical work .......................................................................................... 6
7. Duct work (Fig. 7-1) ............................................................................... 10
8. Test run .................................................................................................. 10
9. Easy maintenance function .................................................................... 13

 Warning:

• The unit must not be installed by the user. Ask a dealer or an authorized

technician to install the unit. If the unit is installed incorrectly, water leakage,
electric shock, or fire may result.

• For installation work, follow the instructions in the Installation Manual and

use tools and pipe components specifically made for use with R410A refrig-
erant. The R410A refrigerant in the HFC system is pressurized 1.6 times the
pressure of usual refrigerants. If pipe components not designed for R410A
refrigerant are used and the unit is not installed correctly, the pipes may burst
and cause damage or injuries. In addition, water leakage, electric shock, or
fire may result.

• The unit must be installed according to the instructions in order to minimize

the risk of damage from earthquakes, typhoons, or strong winds. An incor-
rectly installed unit may fall down and cause damage or injuries.

• The unit must be securely installed on a structure that can sustain its weight.

If the unit is mounted on an unstable structure, it may fall down and cause
damage or injuries.

• If the air conditioner is installed in a small room, measures must be taken to

prevent the refrigerant concentration in the room from exceeding the safety
limit in the event of refrigerant leakage. Consult a dealer regarding the appro-
priate measures to prevent the allowable concentration from being exceeded.
Should the refrigerant leak and cause the concentration limit to be exceeded,
hazards due to lack of oxygen in the room may result.

• Ventilate the room if refrigerant leaks during operation. If refrigerant comes

into contact with a flame, poisonous gases will be released.

• All electric work must be performed by a qualified technician according to

local regulations and the instructions given in this manual. The units must be
powered by dedicated power lines and the correct voltage and circuit break-
ers must be used. Power lines with insufficient capacity or incorrect electri-
cal work may result in electric shock or fire.

• Use C1220 copper phosphorus, for copper and copper alloy seamless pipes,

to connect the refrigerant pipes. If the pipes are not connected correctly, the
unit will not be properly grounded and electric shock may result.

• Use only specified cables for wiring. The connections must be made securely

without tension on the terminals. If the cables are connected or installed in-
correctly, overheating or fire may result.

• The terminal block cover of the outdoor unit must be firmly attached. If the

cover is mounted incorrectly and dust and moisture enter the unit, electric
shock or fire may result.

• When installing or moving the air conditioner, use only the specified refriger-

ant (R410A) to charge the refrigerant lines. Do not mix it with any other refrig-
erant and do not allow air to remain in the lines. Air enclosed in the lines can
cause pressure peaks resulting in a rupture and other hazards.

• Use only accessories authorized by Mitsubishi Electric and ask a dealer or

an authorized technician to install them. If accessories are incorrectly in-
stalled, water leakage, electric shock, or fire may result.

• Do not alter the unit. Consult a dealer for repairs. If alterations or repairs are

not performed correctly, water leakage, electric shock, or fire may result.

• The user should never attempt to repair the unit or transfer it to another loca-

tion. If the unit is installed incorrectly, water leakage, electric shock, or fire
may result. If the air conditioner must be repaired or moved, ask a dealer or
an authorized technician.

• After installation has been completed, check for refrigerant leaks. If refriger-

ant leaks into the room and comes into contact with the flame of a heater or
portable cooking range, poisonous gases will be released.

1.1. Before installation

 Caution:

• Do not use the unit in an unusual environment. If the air conditioner is in-

stalled in areas exposed to steam, volatile oil (including machine oil), or sulfuric
gas, areas exposed to high salt content such as the seaside, or areas where
the unit will be covered by snow, the performance can be significantly re-
duced and the internal parts can be damaged.

• Do not install the unit where combustible gases may leak, be produced, flow,

or accumulate. If combustible gas accumulates around the unit, fire or explo-
sion may result.

• Do not keep food, plants, caged pets, artwork, or precision instruments in the

direct airflow of the indoor unit or too close to the unit, as these items can be
damaged by temperature changes or dripping water.

• When the room humidity exceeds 80% or when the drainpipe is clogged, wa-

ter may drip from the indoor unit. Do not install the indoor unit where such
dripping can cause damage. The outdoor unit produces condensation during
the heating operation. Make sure to provide drainage around the outdoor unit
if such condensation is likely to cause damage.

• When installing the unit in a hospital or communications office, be prepared

for noise and electronic interference. Inverters, home appliances, high-fre-
quency medical equipment, and radio communications equipment can cause
the air conditioner to malfunction or breakdown. The air conditioner may also
affect medical equipment, disturbing medical care, and communications equip-
ment, harming the screen display quality.

1.2. Before installation (relocation)

 Caution:

• Be extremely careful when transporting the units. Two or more persons are

needed to handle the unit, as it weighs 20 kg or more. Do not grasp the pack-
aging bands. Wear protective gloves to remove the unit from the packaging
and to move it, as you can injure your hands on the fins or other parts.

• Be sure to safely dispose of the packaging materials. Packaging materials,

such as nails and other metal or wooden parts may cause stabs or other
injuries.

• Thermal insulation of the drainpipe is necessary to prevent condensation. If

the drainpipe is not properly insulated, condensation will be formed and the
ceiling, floor, or important items may be damaged.

• Install the drainpipe according to this Installation Manual to ensure proper

drainage. Place thermal insulation on the pipes to prevent condensation. If
the drainpipe is installed incorrectly, water leakage and damage to the ceil-
ing, floor, furniture, or other possessions may result.

• The base and attachments of the outdoor unit must be periodically checked

for looseness, cracks or other damage. If such defects are left uncorrected,
the unit may fall down and cause damage or injuries.

• Do not clean the air conditioner unit with water. Electric shock may result.
• Tighten all flare nuts to specification using a torque wrench. If tightened too

much, the flare nut can break after an extended period and refrigerant can
leak out.

Содержание Mr.Slim PEA-RP100EA

Страница 1: ...glish INSTALLATION MANUAL For safe and correct use read this manual and the outdoor unit installation manual thoroughly before installing the air conditioner unit Air Conditioners PEA RP EA FOR INSTALLER ...

Страница 2: ...o charge the refrigerant lines Do not mix it with any other refrig erant and do not allow air to remain in the lines Air enclosed in the lines can cause pressure peaks resulting in a rupture and other hazards Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them If accessories are incorrectly in stalled water leakage electric shock or f...

Страница 3: ...ed dust may accumulate and breakdown may result Do not touch any switch with wet hands Electric shock may result Do not touch the refrigerant pipes with bare hands during operation The refrigerant pipes are hot or cold depending on the condition of the flowing refrigerant If you touch the pipes burns or frostbite may result After stopping operation be sure to wait at least five minutes before turn...

Страница 4: ...3 The ceiling work differs according to the construction of the building Building con structors and interior decorators should be consulted for details 1 Wooden structures Use tie beams single storied houses or second floor beams two story houses as reinforcing members Wooden beams for suspending air conditioners must be sturdy and their sides must be at least 6 cm long if the beams are separated ...

Страница 5: ...nd other hazards RP71 140 Liquid pipe ø9 52 thickness 0 8 mm Gas pipe ø15 88 thickness 1 0 mm Do not use pipes thinner than those specified above A Die B Copper pipe A A B Fig 4 2 Copper pipe O D A mm mm Flare tool for R 22 R407C Flare tool for R410A Clutch type ø6 35 1 4 0 0 5 1 0 1 5 ø9 52 3 8 0 0 5 1 0 1 5 ø12 7 1 2 0 0 5 1 0 1 5 ø15 88 5 8 0 0 5 1 0 1 5 ø19 05 3 4 0 0 5 1 0 1 5 4 2 Indoor unit...

Страница 6: ...r Outdoor connecting cable Use buffer bushing to prevent tensile force to the terminal bed F The Indoor Outdoor connecting cables G Tensile force H Knockout hole for the remote controller cables Use ordinary bushing I The remote controller cables s s s s s Selecting non fuse breaker NF or earth leakage breaker NV 4 Installing the refrigerant piping E F D C B 4 3 Refrigerant and drainage piping loc...

Страница 7: ...owever between S3 and S1 these terminals are not electrically insulataed by the transformer or other device Notes 1 Wiring size must comply with the applicable local and national code 2 Power supply cords and indoor unit outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord Design 245 IEC 57 3 Install an earth longer than other cables Indoor unit model Indo...

Страница 8: ...ircuit rating Wiring Wire No size mm 2 There are three types of labels labels A B and C Affix the appropriate labels to the units according to the wiring method Electric heater For models with heater Connectors connections when shipped from the factory are for indoor unit power supplied from outdoor unit Indoor unit power supplied from outdoor unit when shipped from factory If the indoor and outdo...

Страница 9: ... indoor unit 6 5 Function settings Wired remote controller Fig 6 7 Changing the power voltage setting Be sure to change the power voltage setting depending on the voltage used 1 Go to the function setting mode Switch OFF the remote controller Press the A and B buttons simultaneously and hold them for at least 2 seconds FUNCTION will start to flash 2 Use the C button to set the refrigerant address ...

Страница 10: ...sting pipes that carried R22 refrigerant replacement op eration must be performed before performing a test run If new pipes are used these procedures are not necessary If existing pipes that carried R22 refrigerant are used for the RP3 model these procedures are not necessary The replacement operation cannot be performed Replacement operation procedures 1 Supply power 2 Set DIP switch SW8 2 on the...

Страница 11: ...E Check code F Unit address Fig 8 2 ERROR CODE ERROR CODE B F E PAR 21MAA ON OFF FILTER CHECK OPERATION CLEAR TEST TEMP MENU BACK DAY MONITOR SET CLOCK ON OFF ERROR CODE C B A E D 8 Test run Output pattern A Errors detected by indoor unit Beeper sounds OPERATION Symptom Remark INDICATOR lamp flashes Check code Number of times 1 P1 Intake sensor error 2 P2 P9 Pipe Liquid or 2 phase pipe sensor erro...

Страница 12: ...outdoor units Make sure that this LED is always blinking 8 4 Check of drainage During the trial run ensure the water is being properly drained out and that no water is leaking from joints Always check this during installation even if the unit is not required to provide cooling drying at that time 8 Test run Output pattern B Errors detected by unit other than indoor unit outdoor unit etc Beeper sou...

Страница 13: ... press the ON OFF button to deactivate the maintenance mode Stable operation Using the maintenance mode the operation frequency can be fixed and the op eration can be stabilized If the air conditioner is stopped use the following proce dure to start this operation COOL STABLE MODE HEAT STABLE MODE STABLE MODE CANCEL Stable cooling operation Stable heating operation Stable operation cancellation Di...

Страница 14: ......

Страница 15: ......

Страница 16: ...sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Thailand BG79U642H01 ...