background image

10

8. Test run

8.1. Before test run

s

After completing installation and the wiring and piping of the indoor and outdoor
units, check for refrigerant leakage, looseness in the power supply or control
wiring, wrong polarity, and no disconnection of one phase in the supply.

s

Use a 500-volt megohmmeter to check that the resistance between the power
supply terminals and ground is at least 1.0M

.

s

Do not carry out this test on the control wiring (low voltage circuit) terminals.

 Warning:

Do not use the air conditioner if the insulation resistance is less than 1.0M

.

Insulation resistance

After installation or after the power source to the unit has been cut for an extended
period, the insulation resistance will drop below 1 M

 due to refrigerant accumulat-

ing in the compressor. This is not a malfunction. Perform the following procedures.
1. Remove the wires from the compressor and measure the insulation resistance of

the compressor.

2. If the insulation resistance is below 1 M

, the compressor is faulty or the resist-

ance dropped due the accumulation of refrigerant in the compressor.

3. After connecting the wires to the compressor, the compressor will start to warm

up after power is supplied. After supplying power for the times indicated below,
measure the insulation resistance again.

The insulation resistance drops due to accumulation of refrigerant in the com-
pressor. The resistance will rise above 1 M

 after the compressor is warmed

up for two to three hours.
(The time necessary to warm up the compressor varies according to atmos-
pheric conditions and refrigerant accumulation.)

To operate the compressor with refrigerant accumulated in the compressor,
the compressor must be warmed up at least 12 hours to prevent breakdown.

4. If the insulation resistance rises above 1 M

, the compressor is not faulty.

 Caution:

• The compressor will not operate unless the power supply phase connection

is correct.

• Turn on the power at least 12 hours before starting operation.
• Starting operation immediately after turning on the main power switch can

result in severe damage to internal parts. Keep the power switch turned on
during the operational season.

s

The followings must be checked as well.

• The outdoor unit is not faulty. LED1 and LED2 on the control board of the outdoor

unit flash when the outdoor unit is faulty.

• Both the gas and liquid stop valves are completely open.
• A protective sheet covers the surface of the DIP switch panel on the control board of

the outdoor unit. Remove the protective sheet to operate the DIP switches easily.

• Make sure that the all of the SW5 DIP switches for function changes on the control

board of the outdoor unit are set to OFF. If all of the SW5 switches are not set to
OFF, record the settings and then set all of the switches to OFF. Begin recovering
the refrigerant. After moving the unit to a new location and completing the test run,
set the SW5 switches to the previously recorded settings.

Unit replacement operation

s

When reusing existing pipes that carried R22 refrigerant, replacement op-
eration must be performed before performing a test run.

• If new pipes are used, these procedures are not necessary.
• If existing pipes that carried R22 refrigerant are used for the RP3 model, these

procedures are not necessary. (The replacement operation cannot be performed.)

Replacement operation procedures

1

Supply power.

2

Set DIP switch SW8-2 on the control board of the outdoor unit to ON to start
replacement operation.
* The replacement operation is performed using the cooling system. Cool air will

flow from the indoor unit during the replacement operation.

* During the replacement operation,

 

TEST RUN

 

is displayed on the remote controller

and LED1 and LED2 on the control board of the outdoor unit flash together.

3

Replacement operation requires at least two hours to complete.
* After setting switch SW8-2 to ON, the unit automatically stops after two hours.
* Replacement operation can be performed repeatedly by setting switch SW8-2

from OFF to ON. Wait at least two hours before starting replacement operation.
(If operation is started in less than two hours, the existing pipes will not be
cleaned and the unit may be damaged.)

4

Set switch SW8-2 to OFF. (Replacement operation is complete.)
* If the indoor temperature is less than 15°C, the compressor will operate inter-

mittently but the unit is not faulty.

Fig. 7-1

A

F

G

H

I

C

J

K

L

E

M

B

D

M

N

A

Indoor unit

B

Air intake duct flange

C

Drain pan

D

Air outlet duct flange

E

Electrical parts box

F

Air intake

G

Air outlet

H

Leave clearance to prevent
short cycle

I

Ceiling

J

Air intake (procure locally)

K

Air filter (procure locally)

L

Air intake duct (procure locally)

M

Canvas duct (procure locally)

N

Air outlet duct (procure locally)

O

Air outlet grille (procure locally)

Mode
Filter sign

Fan speed

No. of air outlets

Installed options (high-performance filter)

Up/down vane setting

Energy saving air flow
(Heating mode)

Settings
100Hr
2500Hr
No filter sign indicator
Standard (PLH/PLA)/Silent (PCH/PCA)
High ceiling 

1

 (PLH/PLA)/Standard (PCH/PCA)

High ceiling 

2

 (PLH/PLA)/High ceiling (PCH/PCA)

4 directions
3 directions
2 directions
Not supported
Supported
No vanes
Equipped with vanes (vanes angle setup 

1

)

Equipped with vanes (vanes angle setup 

2

)

Disabled
Enabled

Mode no.

Setting no. Initial setting

setting

1

07

2
3
1

08

2

3
1

09

2

3

10

1

2

11

1
2

3

12

1

2

Select unit numbers 01 to 03 or all units (AL [wired remote controller]/07 [wireless remote controller])

*1 When the power supply returns, the air conditioner will start 3 minutes later.
*2 Power failure automatic recovery initial setting depends on the connecting outdoor unit.

7. Duct work (Fig. 7-1)

Use the canvas duct for connecting the indoor unit and the duct.
Use fire-proof material for the duct parts.
Make sure that the duct has sufficient heat insulation.

Notes:
• An outlet duct of 850 mm or more is needed for construction.
• Connect the main body of the air conditioner and the duct so that their

potentials are equal.

• The standard external static pressure should be 125 Pa.
• Connect an earth cable 

R

 from the air intake duct 

E

 to the earth terminal 

Q

.

Then, connect another earth cable 

R

 from the earth terminal 

Q

 to the air

outlet duct 

F

.

6. Electrical work

Содержание Mr.Slim PEA-RP100EA

Страница 1: ...glish INSTALLATION MANUAL For safe and correct use read this manual and the outdoor unit installation manual thoroughly before installing the air conditioner unit Air Conditioners PEA RP EA FOR INSTALLER ...

Страница 2: ...o charge the refrigerant lines Do not mix it with any other refrig erant and do not allow air to remain in the lines Air enclosed in the lines can cause pressure peaks resulting in a rupture and other hazards Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them If accessories are incorrectly in stalled water leakage electric shock or f...

Страница 3: ...ed dust may accumulate and breakdown may result Do not touch any switch with wet hands Electric shock may result Do not touch the refrigerant pipes with bare hands during operation The refrigerant pipes are hot or cold depending on the condition of the flowing refrigerant If you touch the pipes burns or frostbite may result After stopping operation be sure to wait at least five minutes before turn...

Страница 4: ...3 The ceiling work differs according to the construction of the building Building con structors and interior decorators should be consulted for details 1 Wooden structures Use tie beams single storied houses or second floor beams two story houses as reinforcing members Wooden beams for suspending air conditioners must be sturdy and their sides must be at least 6 cm long if the beams are separated ...

Страница 5: ...nd other hazards RP71 140 Liquid pipe ø9 52 thickness 0 8 mm Gas pipe ø15 88 thickness 1 0 mm Do not use pipes thinner than those specified above A Die B Copper pipe A A B Fig 4 2 Copper pipe O D A mm mm Flare tool for R 22 R407C Flare tool for R410A Clutch type ø6 35 1 4 0 0 5 1 0 1 5 ø9 52 3 8 0 0 5 1 0 1 5 ø12 7 1 2 0 0 5 1 0 1 5 ø15 88 5 8 0 0 5 1 0 1 5 ø19 05 3 4 0 0 5 1 0 1 5 4 2 Indoor unit...

Страница 6: ...r Outdoor connecting cable Use buffer bushing to prevent tensile force to the terminal bed F The Indoor Outdoor connecting cables G Tensile force H Knockout hole for the remote controller cables Use ordinary bushing I The remote controller cables s s s s s Selecting non fuse breaker NF or earth leakage breaker NV 4 Installing the refrigerant piping E F D C B 4 3 Refrigerant and drainage piping loc...

Страница 7: ...owever between S3 and S1 these terminals are not electrically insulataed by the transformer or other device Notes 1 Wiring size must comply with the applicable local and national code 2 Power supply cords and indoor unit outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord Design 245 IEC 57 3 Install an earth longer than other cables Indoor unit model Indo...

Страница 8: ...ircuit rating Wiring Wire No size mm 2 There are three types of labels labels A B and C Affix the appropriate labels to the units according to the wiring method Electric heater For models with heater Connectors connections when shipped from the factory are for indoor unit power supplied from outdoor unit Indoor unit power supplied from outdoor unit when shipped from factory If the indoor and outdo...

Страница 9: ... indoor unit 6 5 Function settings Wired remote controller Fig 6 7 Changing the power voltage setting Be sure to change the power voltage setting depending on the voltage used 1 Go to the function setting mode Switch OFF the remote controller Press the A and B buttons simultaneously and hold them for at least 2 seconds FUNCTION will start to flash 2 Use the C button to set the refrigerant address ...

Страница 10: ...sting pipes that carried R22 refrigerant replacement op eration must be performed before performing a test run If new pipes are used these procedures are not necessary If existing pipes that carried R22 refrigerant are used for the RP3 model these procedures are not necessary The replacement operation cannot be performed Replacement operation procedures 1 Supply power 2 Set DIP switch SW8 2 on the...

Страница 11: ...E Check code F Unit address Fig 8 2 ERROR CODE ERROR CODE B F E PAR 21MAA ON OFF FILTER CHECK OPERATION CLEAR TEST TEMP MENU BACK DAY MONITOR SET CLOCK ON OFF ERROR CODE C B A E D 8 Test run Output pattern A Errors detected by indoor unit Beeper sounds OPERATION Symptom Remark INDICATOR lamp flashes Check code Number of times 1 P1 Intake sensor error 2 P2 P9 Pipe Liquid or 2 phase pipe sensor erro...

Страница 12: ...outdoor units Make sure that this LED is always blinking 8 4 Check of drainage During the trial run ensure the water is being properly drained out and that no water is leaking from joints Always check this during installation even if the unit is not required to provide cooling drying at that time 8 Test run Output pattern B Errors detected by unit other than indoor unit outdoor unit etc Beeper sou...

Страница 13: ... press the ON OFF button to deactivate the maintenance mode Stable operation Using the maintenance mode the operation frequency can be fixed and the op eration can be stabilized If the air conditioner is stopped use the following proce dure to start this operation COOL STABLE MODE HEAT STABLE MODE STABLE MODE CANCEL Stable cooling operation Stable heating operation Stable operation cancellation Di...

Страница 14: ......

Страница 15: ......

Страница 16: ...sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Thailand BG79U642H01 ...

Отзывы: