INSTALLATION MANUAL

For safe and correct use, read this manual and the outdoor unit installation manual thoroughly before installing 

the air-conditioner unit.

Air-Conditioners

PEA-RP·EAQ

FOR INSTALLER

English

RG79D318H02_cover.indd   1

12/6/2010   1:27:23 PM

Содержание Mr.Slim PEA-RP-EAQ

Страница 1: ...STALLATION MANUAL For safe and correct use read this manual and the outdoor unit installation manual thoroughly before installing the air conditioner unit Air Conditioners PEA RP EAQ FOR INSTALLER English ...

Страница 2: ...garding the appro priate measures to prevent the allowable concentration from being exceeded Should the refrigerant leak and cause the concentration limit to be exceeded hazards due to lack of oxygen in the room may result Ventilate the room if refrigerant leaks during operation If refrigerant comes into contact with a flame poisonous gases will be released All electric work must be performed by a...

Страница 3: ...akdown may result 1 2 Before installation relocation Caution Be extremely careful when transporting the units Two or more persons are needed to handle the unit as it weighs 20 kg or more Do not grasp the pack aging bands Wear protective gloves to remove the unit from the packaging and to move it as you can injure your hands on the fins or other parts Be sure to safely dispose of the packaging mate...

Страница 4: ...en beams for suspending air conditioners must be sturdy and their sides must be at least 6 cm long if the beams are separated by not more than 90 cm and their sides must be at least 9 cm long if the beams are separated by as much as 180 cm The size of the suspension bolts should be ø10 3 8 The bolts do not come with the unit 2 Ferro concrete structures Secure the suspension bolts using the method ...

Страница 5: ... pipes are used wrap liquid and gas pipes with commercially available insulation materials heat resistant to 100 C or more thickness of 12 mm or more The indoor parts of the drain pipe should be wrapped with polyethylene foam insula tion materials specific gravity of 0 03 thickness of 9 mm or more Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening flare nut Use...

Страница 6: ...ecting cable Use buffer bushing to prevent tensile force to the terminal bed F The Indoor Outdoor connecting cables G Tensile force H Knockout hole for the remote controller cables Use ordinary bushing I The remote controller cables Selecting non fuse breaker NF or earth leakage breaker NV 4 Installing the refrigerant piping 4 3 Refrigerant and drainage piping locations of indoor unit Fig 4 3 A Re...

Страница 7: ...are not electrically insulated by the transformer or other device Notes 1 Wiring size must comply with the applicable local and national code 2 Power supply cords and indoor unit outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord Design 245 IEC 57 3 Install an earth longer than other cables For models without heater For models with heater For models with...

Страница 8: ...ve separate power supplies change the connections of the connectors as shown in the following figure Connectors Indoor unit control board Separate indoor unit outdoor unit power supplies Electric heater For models with heater Indoor unit control board 6 3 Separate indoor unit outdoor unit power supplies For PUHZ application only The following connection patterns are available The outdoor unit powe...

Страница 9: ...oltage setting Be sure to change the power voltage setting depending on the voltage used 1 Go to the function setting mode Switch OFF the remote controller Press the A and B buttons simultaneously and hold them for at least 2 seconds FUNCTION will start to flash 2 Use the C button to set the refrigerant address 3 to 00 3 Press D and will start to flash in the unit number 4 display 4 Use the C butt...

Страница 10: ...set to OFF record the settings and then set all of the switches to OFF Begin recovering the refrigerant After moving the unit to a new location and completing the test run set the SW5 switches to the previously recorded settings Unit replacement operation When reusing existing pipes that carried R22 refrigerant replacement opera tion must be performed before performing a test run If new pipes are ...

Страница 11: ... Check code F Unit address Fig 8 2 8 Test run OPERATION INDICATOR lamp flash pattern Beep Beep Beep Beep Beep Beep Beep Off Approx 2 5 sec On Approx 3 sec On 0 5 sec On 0 5 sec On 0 5 sec On 0 5 sec Off Approx 2 5 sec On Approx 3 sec On 0 5 sec On 0 5 sec Repeated Number of flashes beeps in pattern indicates the check code in the following table i e n 5 for P5 Number of flashes beeps in pattern in...

Страница 12: ...gnal was received and the OPERATION INDICATOR lamp does not come on there are no error records 2 If the beeper sounds three times continuously beep beep beep 0 4 0 4 0 4 sec after the initial two beeps to confirm the self check start signal was received the specified refrigerant address is incorrect On wired remote controller Check code displayed in the LCD If the unit cannot be operated properly ...

Страница 13: ...ation frequency can be fixed and the operation can be stabilized If the air conditioner is stopped use the following procedure to start this operation Stable cooling operation Stable heating operation Stable operation cancellation Display A Press the button to select the operation mode Press the button Waiting for stable operation Display D Stable operation 10 20 min You can check the data using s...

Страница 14: ......

Страница 15: ......

Страница 16: ... 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Thailand RG79D318H02 This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC ...