Note:

Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)

For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.

8.4.  Check of drainage

•  During the trial run, ensure the water is being properly drained out and that no water is leaking from joints.

•  Always check this during installation even if the unit is not required to provide cooling/drying at that time.

8.  Test run

[Output pattern B]  Errors detected by unit other than indoor unit (outdoor unit, etc.)

Wireless remote controller

Wired remote 

controller

Symptom

Remark

Beeper sounds/OPERATION 

INDICATOR lamp flashes 

(Number of times)

Check code

1

E9

Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)

For details, check the LED 

display of the outdoor controller 

board.

2

UP

Compressor overcurrent interruption

3

U3, U4

Open/short of outdoor unit thermistors

4

UF

Compressor overcurrent interruption (When compressor locked)

5

U2

Abnormal high discharging temperature/49C worked/insufficient refrigerant

6

U1, Ud

Abnormal high pressure (63H worked)/Overheating safeguard operation

7

U5

Abnormal temperature of heat sink

8

U8

Outdoor unit fan safeguard stop

9

U6

Compressor overcurrent interruption/Abnormal of power module

10

U7

Abnormality of super heat due to low discharge temperature

11

U9, UH

Abnormality such as overvoltage or voltage shortage and abnormal synchronous 

signal to main circuit/Current sensor error

12

13

14

Others

Other errors (Refer to the technical manual for the outdoor unit.)

*1. If the beeper does not sound again after the initial two beeps to confirm the self-check start signal was received and the OPERATION INDICATOR lamp does not come 

on, there are no error records.

*2. If the beeper sounds three times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial two beeps to confirm the self-check start signal was received, the 

specified refrigerant address is incorrect.

•  On wired remote controller

  Check code displayed in the LCD.

•  If the unit cannot be operated properly after the above test run has been performed, refer to the following table to remove the cause.

Symptom

Cause

Wired remote controller

LED 1, 2 (PCB in outdoor unit)

PLEASE WAIT

For about 2 minutes 

following power-on

After LED 1, 2 are lighted, LED 2 is turned 

off, then only LED 1 is lighted.  

(Correct operation)

• For about 2 minutes following power-on, operation of 

the  remote  controller  is  not  possible  due  to  system 

start-up. (Correct operation)

PLEASE WAIT 

 Error code

After about 2 minutes 

has expired following 

power-on

Only LED 1 is lighted. 

 LED 1, 2 blink.

• Connector for the outdoor unit’s protection device is 

not connected.

• Reverse or open phase wiring for the outdoor unit’s 

power terminal block (L1, L2, L3)

Display messages do not appear even 

when operation switch is turned ON 

(operation lamp does not light up).

Only LED 1 is lighted. 

 LED 1 blinks twice, 

LED 2 blinks once.

• Incorrect  wiring  between  indoor  and  outdoor  units 

(incorrect polarity of S1, S2, S3)

• Remote controller wire short

LED 1 (power for microcomputer)

Indicates whether control power is supplied. Make sure that this LED is always lit.

LED 2 (power for remote controller)

Indicates whether power is supplied to the remote controller. This LED lights only in the case of the 

indoor unit which is connected to the outdoor unit refrigerant address “0”.

LED 3 (communication between indoor and outdoor units)

Indicates state of communication between the indoor and outdoor units. Make sure that this LED is 

always blinking.

RG79D318H02.indd   12

12/6/2010   1:26:46 PM

Содержание Mr.Slim PEA-RP-EAQ

Страница 1: ...STALLATION MANUAL For safe and correct use read this manual and the outdoor unit installation manual thoroughly before installing the air conditioner unit Air Conditioners PEA RP EAQ FOR INSTALLER English ...

Страница 2: ...garding the appro priate measures to prevent the allowable concentration from being exceeded Should the refrigerant leak and cause the concentration limit to be exceeded hazards due to lack of oxygen in the room may result Ventilate the room if refrigerant leaks during operation If refrigerant comes into contact with a flame poisonous gases will be released All electric work must be performed by a...

Страница 3: ...akdown may result 1 2 Before installation relocation Caution Be extremely careful when transporting the units Two or more persons are needed to handle the unit as it weighs 20 kg or more Do not grasp the pack aging bands Wear protective gloves to remove the unit from the packaging and to move it as you can injure your hands on the fins or other parts Be sure to safely dispose of the packaging mate...

Страница 4: ...en beams for suspending air conditioners must be sturdy and their sides must be at least 6 cm long if the beams are separated by not more than 90 cm and their sides must be at least 9 cm long if the beams are separated by as much as 180 cm The size of the suspension bolts should be ø10 3 8 The bolts do not come with the unit 2 Ferro concrete structures Secure the suspension bolts using the method ...

Страница 5: ... pipes are used wrap liquid and gas pipes with commercially available insulation materials heat resistant to 100 C or more thickness of 12 mm or more The indoor parts of the drain pipe should be wrapped with polyethylene foam insula tion materials specific gravity of 0 03 thickness of 9 mm or more Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening flare nut Use...

Страница 6: ...ecting cable Use buffer bushing to prevent tensile force to the terminal bed F The Indoor Outdoor connecting cables G Tensile force H Knockout hole for the remote controller cables Use ordinary bushing I The remote controller cables Selecting non fuse breaker NF or earth leakage breaker NV 4 Installing the refrigerant piping 4 3 Refrigerant and drainage piping locations of indoor unit Fig 4 3 A Re...

Страница 7: ...are not electrically insulated by the transformer or other device Notes 1 Wiring size must comply with the applicable local and national code 2 Power supply cords and indoor unit outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord Design 245 IEC 57 3 Install an earth longer than other cables For models without heater For models with heater For models with...

Страница 8: ...ve separate power supplies change the connections of the connectors as shown in the following figure Connectors Indoor unit control board Separate indoor unit outdoor unit power supplies Electric heater For models with heater Indoor unit control board 6 3 Separate indoor unit outdoor unit power supplies For PUHZ application only The following connection patterns are available The outdoor unit powe...

Страница 9: ...oltage setting Be sure to change the power voltage setting depending on the voltage used 1 Go to the function setting mode Switch OFF the remote controller Press the A and B buttons simultaneously and hold them for at least 2 seconds FUNCTION will start to flash 2 Use the C button to set the refrigerant address 3 to 00 3 Press D and will start to flash in the unit number 4 display 4 Use the C butt...

Страница 10: ...set to OFF record the settings and then set all of the switches to OFF Begin recovering the refrigerant After moving the unit to a new location and completing the test run set the SW5 switches to the previously recorded settings Unit replacement operation When reusing existing pipes that carried R22 refrigerant replacement opera tion must be performed before performing a test run If new pipes are ...

Страница 11: ... Check code F Unit address Fig 8 2 8 Test run OPERATION INDICATOR lamp flash pattern Beep Beep Beep Beep Beep Beep Beep Off Approx 2 5 sec On Approx 3 sec On 0 5 sec On 0 5 sec On 0 5 sec On 0 5 sec Off Approx 2 5 sec On Approx 3 sec On 0 5 sec On 0 5 sec Repeated Number of flashes beeps in pattern indicates the check code in the following table i e n 5 for P5 Number of flashes beeps in pattern in...

Страница 12: ...gnal was received and the OPERATION INDICATOR lamp does not come on there are no error records 2 If the beeper sounds three times continuously beep beep beep 0 4 0 4 0 4 sec after the initial two beeps to confirm the self check start signal was received the specified refrigerant address is incorrect On wired remote controller Check code displayed in the LCD If the unit cannot be operated properly ...

Страница 13: ...ation frequency can be fixed and the operation can be stabilized If the air conditioner is stopped use the following procedure to start this operation Stable cooling operation Stable heating operation Stable operation cancellation Display A Press the button to select the operation mode Press the button Waiting for stable operation Display D Stable operation 10 20 min You can check the data using s...

Страница 14: ......

Страница 15: ......

Страница 16: ... 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Thailand RG79D318H02 This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC ...

Отзывы: