30
31
9-7. TEST POINT DIAGRAM
Indoor controller board
PCY-P18KA.TH PCY-P24KA.TH
PCY-P30KA.TH
PCY-P36KA.TH PCY-P42KA.TH
PCY-P48KA.TH
SW2
Capacity setting
SW1
Model selection
CN2L
Connector (LOSSNAY)
CN41
Connector
(HA terminal-A)
CN90
Connect to the wireless
remote controller board
(CNB)
CN20
Room temperature
thermistor (TH1)
CN22
Connect to the terminal block (TB5)
(Remote controller connecting wire)
(10.4~14.6VDC)
LED2
Power supply (R.B)
LED1
Power supply (I.B)
CNP
Drain-pump output (DP)
(220-240 V AC)
CN01
Connect to the Terminal Block (TB2)
Between
3
and
5
220-240 V AC
CNV
Vane motor output (MV)
12 V pulse output
SWE
Emergency operation
Jumper wire J41, J42
Pair No. setting for wireless
remote controller
FUSE 6.3 A /250 V
CNMF
Fan motor
1
-
4
: DC 310~340 V
5
-
4
: DC 15 V
6
-
4
: DC 0~6.5 V
7
-
4
: Stop DC0 or 15 V
Operation DC7.5 V
(0~15 pulse)
V
CC
: Voltage between pins of
C955 15 V DC
(Same as
5
(+)–
4
(-) of CNMF)
CN44
Pipe temperature
thermistor
1
-
2
: Liquid (TH2)
3
-
4
: Cond./Eva. (TH5)
CN4F
Drain float switch (FS)
CN51
Centrally control
1
-
2
: Control signal
13VDC pulse input (
1
: +)
3
-
4
: Operation indicator
13VDC (
3
: +)
3
-
5
: Malfunction indicator
13VDC (
3
: +)
LED3
Transmission
(Indoor/outdoor)
CN105
CN3C
Transmission
(Indoor/outdoor)
(0~24VDC)
OCH550A
Содержание Mr.Slim PCY-P18KA.TH