6. Electrical work

Fig. 6-8

?

Mode number

?

Setting number

?

Refrigerant address

?

Unit number

1

2

3

4

6.3. Function settings

6.3.1 Function setting on the unit (Selecting the unit functions)

1) For wired remote controller (Fig. 6-8)

Changing the power voltage setting
• Be sure to change the power voltage setting depending on the voltage used.

1

Go to the function setting mode.

Switch OFF the remote controller.
Press the 

A

 and 

B

 buttons simultaneously and hold them for at least 2

seconds. FUNCTION will start to flash.

2

Use the 

C

 button to set the refrigerant address (

3

) to 00.

3

Press 

D

 and [--] will start to flash in the unit number (

4

) display.

4

Use the 

C

 button to set the unit number (

4

) to 00.

5

Press the 

E

 MODE button to designate the refrigerant address/unit number. [--]

will flash in the mode number (

1

) display momentarily.

6

Press the 

F

 buttons to set the mode number (

1

) to 04.

7

Press the 

G

 button and the current set setting number (

2

) will flash.

Use the 

F

 button to switch the setting number in response to the power supply

voltage to be used.
Power supply voltage

230 V : setting number = 1
208 V : setting number = 2

8

Press the MODE button 

E

 and mode and the setting number (

1

) and (

2

) will

change to being on constantly and the contents of the setting can be confirmed.

9

Press the FILTER 

A

 and TEST RUN 

B

 buttons simultaneously for at least two

seconds. The function selection screen will disappear momentarily and the air
conditioner OFF display will appear.

2) For wireless remote controller (Fig. 6-9)

Changing the power voltage setting
• Be sure to change the power voltage setting depending on the voltage used.

1

Go to the function select mode

Press the 

CHECK

 button 

F

 twice continuously.

(Start this operation from the status of remote controller display turned off.)

CHECK

 is lighted and “00” blinks.

Press the temp 

 button 

C

 once to set “50”. Direct the wireless remote controller

toward the receiver of the indoor unit and press the 

h

 button 

A

.

2

Setting the unit number

Press the temp 

 

 button 

C

 and 

D

 to set the unit number “00”. Direct the wire-

less remote controller toward the receiver of the indoor unit and press the 

min

button 

B

.

3

Selecting a mode

Enter 04 to change the power voltage setting using the 

 

C

 and 

 

D

 buttons.

Direct the wireless remote controller toward the receiver of the indoor unit and press

the 

h

 button 

A

.

Current setting number:

1 = 1 beep (one second)
2 = 2 beeps (one second each)
3 = 3 beeps (one second each)

4

Selecting the setting number

Use the 

 

C

 and 

 

D

 buttons to change the power voltage setting to 01 (240 V).

Direct the wireless remote controller toward the sensor of the indoor unit and press

the 

h

 button 

A

.

5

To select multiple functions continuously

Repeat steps 

3

 and 

4

 to change multiple function settings continuously.

6

Complete function selection

Direct the wireless remote controller toward the sensor of the indoor unit and press

the 

 button 

E

.

Note:
Whenever changes are made to the function settings after installation or main-
tenance, be sure to record the changes with a mark in the “Setting” column of
the Function table.

6.3.2 Function setting on the remote controller

Refer to the indoor unit operation manual.

3

CHECK

4

CHECK

ON/OFF

  TEMP

FAN

VANE

TEST RUN

AUTO STOP

AUTO START

h

min

LOUVER

MODE

CHECK

RESET

SET

CLOCK

CHECK

E

C

,

D

F

A

B

Fig. 6-9

2

CHECK

CHECK

1

Function table

Select unit number 00

Mode
Power failure automatic recovery

Indoor temperature detecting

LOSSNAY connectivity

Power voltage

Auto mode (only for PUZ)

Settings
Not available
Available

*1

Indoor unit operating average
Set by indoor unit’s remote controller
Remote controller’s internal sensor
Not Supported
Supported (indoor unit is not equipped with outdoor-air intake)
Supported (indoor unit is equipped with outdoor-air intake)
230 V
208 V
Energy saving cycle automatically enabled
Energy saving cycle automatically disabled

Mode no.

Setting no. Initial setting

Setting

01

1
2
1

02

2
3
1

03

2
3

04

1
2

05

1
2

 BG79U827H01_en

06.5.18, 10:13

11

Содержание Mr. SLIM PCA-A GA Series

Страница 1: ...roughly before installing the air conditioner unit FOR INSTALLER Español MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad exterior antes de instalar la unidad de aire acondicionado PARA EL INSTALADOR BG79U827H01_cover 06 5 18 10 00 1 MITSUBISHI l ELECTRIC m Ir sl 11m ...

Страница 2: ...can be damaged by temperature changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged wa ter may drip from the indoor unit Do not install the indoor unit where such dripping can cause damage When installing the unit in a hospital or communications office be prepared for noise and electronic interference Inverters home appliances high fre quency medical equipmen...

Страница 3: ... 8 Wired remote controller 1 pc Fig 2 1 2 1 Outline dimensions Indoor unit Fig 2 1 Select a proper position allowing the following clearances for installation and mainte nance inch Models W D H A B C E A24 A30 1310 680 221 Min 270 Min 300 Min 500 Max 250 51 9 16 26 7 32 8 9 32 Min 10 5 8 Min 11 13 16 Min 19 11 16 Max 9 13 16 A36 A42 1310 680 281 Min 270 Min 300 Min 500 Max 250 51 9 16 26 7 32 10 5...

Страница 4: ...rocedures 1 Install the washer 1 supplied with the unit and the nut to be locally procured 2 Set hook the unit through the suspending bolts 3 Tighten the nuts Check the unit installing condition Check that the unit is horizontal between the right and left sides Check that the unit slopes continuously downward from the front to the rear When embedding pipes into the wall 2 Installing the suspending...

Страница 5: ...inch or more Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening flare nut Use two wrenches to tighten piping connections Use refrigerant piping insulation provided to insulate indoor unit connections Insu late carefully A Flare cutting dimensions 90 0 5 øA R 1 6 4 t o R 1 3 2 A 45 2 B C D Fig 4 1 4 3 Insulating pipes Fig 4 2 1 Slide the supplied pipe cover 2 ov...

Страница 6: ...rvice entrance H Terminal block for power supply separate indoor outdoor unit power supplies K control application I Terminal block for indoor and outdoor units connection J Terminal block for remote controller K Grounding cable connector Fig 6 1 6 Electrical work A Drain pan B Drain tubing VP20 C Socket cover 6 D Joint socket 5 E Drain tubing cover 7 F Drain tubing sensor 5 Drainage piping work B...

Страница 7: ...en S3 and S1 these terminals are not electrically insulataed by the transformer or other device Notes 1 Wiring size must comply with the applicable local and national code 2 Use copper supply wires 3 Use wires rated 300V or more for the power supply cables and the indoor unit outdoor unit connecting cables 4 Install an earth longer than other cables Indoor unit model Indoor unit power supply Minim...

Страница 8: ...ational code 2 Use copper supply wires 3 Use wires rated 300V or more for the power supply cables 4 Install an earth longer than other cables Indoor unit model Indoor unit power supply Minimum circuit ampacity Maximum rating of overcurrent protective device Indoor unit power supply Indoor unit power supply earth Indoor unit Outdoor unit 1 Indoor unit earth Remote controller Indoor unit 2 Indoor un...

Страница 9: ...208 230 V DC12 V DC12 V DC12 V Circuit rating Wiring Wire No size For heat pump models 1 SW5 Set the DIP switch of the indoor unit control board SW5 1 ON SW5 2 3 OFF 2 3 1 SW5 Set the DIP switch of the indoor unit control board SW5 1 2 ON SW5 3 OFF 2 3 For cooling only models OFF ON SW5 1 A CONTROL K CONTROL SW5 2 heat pump models cooling only models SW5 3 MAIN SUB To change to K control set the D...

Страница 10: ...CT blinks and Model No is lighted 2 Press the min button twice continuously Pair No 0 blinks 3 Press the temp button to set the pair number you want to set 4 Press the SET button with something sharp at the end Set pair number is lighted for three seconds then turned off D B 1 C A 2 ON OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOUVER MODE CHECK RESET SET CLOCK MODELSELECT 2 4 3 A Fig 6...

Страница 11: ...etting the unit number Press the temp button C and D to set the unit number 00 Direct the wire less remote controller toward the receiver of the indoor unit and press the min button B 3 Selecting a mode Enter 04 to change the power voltage setting using the C and D buttons Direct the wireless remote controller toward the receiver of the indoor unit and press the h button A Current setting number 1...

Страница 12: ...e Fan speed button Make sure that the wind speed is switched 6 Check operation of the outdoor unit fan 7 Release test run by pressing the ON OFF button Stop 8 Register a telephone number The telephone number of the repair shop sales office etc to contact if an error occurs can be registered in the remote controller The telephone number will be displayed when an error occurs For registration proced...

Страница 13: ...F Unit address 7 3 2 Wireless remote controller Fig 7 4 1 Turn on the power 2 Press the CHECK button twice Start this operation from the status of remote controller display turned off A CHECK begins to light B 00 begins to blink 3 While pointing the remote controller toward the unit s receiver press the h button The check code will be indicated by the number of times that the buzzer sounds from th...

Страница 14: ...ways lit LED 2 power for remote controller Indicates whether power is supplied to the remote controller This LED lights only in the case of the indoor unit which is connected to the outdoor unit refrigerant address 0 LED 3 communication between indoor and outdoor units only Indicates state of communication between the indoor and outdoor units Make sure that this LED is A control always blinking Ou...

Страница 15: ...he op eration can be stabilized If the air conditioner is stopped use the following proce dure to start this operation COOL STABLE MODE HEAT STABLE MODE STABLE MODE CANCEL Stable cooling operation Stable heating operation Stable operation cancellation Display A Press the MODE button to select the operation mode Press the FILTER button Waiting for stable operation Display D Stable operation 10 20 m...

Страница 16: ...r o demasiado cerca de ella ya que los cambios de temperatura o el agua que gotea podrían dañarlos Cuando la humedad de la habitación supera el 80 o cuando el tubo de drenaje esté obstruido puede gotear agua de la unidad interior No instale la unidad interior en lugares donde el goteo pueda causar daños Si instala la unidad en un hospital o en un centro de comunicaciones recuer de que la unidad pr...

Страница 17: ...ara la tubería del gas 3 Tapón de tubería 1 Tamaño pequeño para la tubería del líquido 4 Bandas 4 5 Adaptador de junta 1 marcado UNIT 6 Tapón para el adaptador 1 7 Tapón para la tubería 1 de drenaje 8 Controlador remoto cableado 1 Fig 2 1 1 2 3 4 5 6 7 Fig 3 1 Fig 3 2 Fig 3 3 E D H C W A B U N IT A C B 26 3 4 12 19 32 3 19 28 5 7 16 2 61 64 3 3 8 3 5 8 7 16 D E 1 13 16 F H D G E H G K J F 1 11 16 ...

Страница 18: ...anche la unidad por medio de los pernos de suspensión 3 Apriete las tuercas Comprobación de las condiciones de instalación de la unidad Comprobar que la unidad haya quedado en posición horizontal de izquierda a dere cha Comprobar que la parte frontal ha quedado ligeramente más levantada que la par te posterior Empotrado de tubos en la pared 2 Instalación en el techo en primer lugar del soporte de ...

Страница 19: ...ves de apriete para apretar las conexiones de los tubos Utilice el aislante de tubería de refrigerante suministrado para aislar las conexio nes de la unidad interior Realice los aislamientos con cuidado B Torsión de apriete de la tuerca abocardada Tubo de cobre O D Tuerca de abocardado Torsión de apriete mm inch O D mm inch N m ft lbs ø6 35 1 4 17 43 64 14 18 10 13 ø9 52 3 8 22 7 8 34 42 25 30 ø12...

Страница 20: ...depósito de drenaje con 1 litro 1 4 gal aproximado de agua vertida desde la abertura de acceso del sensor del tubo 2 Compruebe el desagüe 3 Después de comprobar el correcto funcionamiento del drenaje volver a poner el tapón de la abertura de acceso del sensor del tubo A Depósito de drenaje B Tubo de drenaje VP20 C Tapón del adaptador 6 D Adaptador de junta 5 E Tapón del tubo de dre naje 7 F Sensor...

Страница 21: ...os eléctricamente por el transformador u otro dispositivo Notas 1 El diámetro de los cables debe cumplir la normativa local y nacional 2 Utilice cables de cobre 3 Utilice cables con un régimen nominal de 300 V o superior para los cables de la fuente de alimentación y los cables de conexión de las unidades interior exterior 4 Instale un cable de toma de tierra más largo que el resto de los cables M...

Страница 22: ...C12 V Conectores cuando la unidad se suministra de fábrica las conexiones están realizadas para alimentación de la unidad interior sumi nistrada desde la unidad exterior Alimentación de la unidad interior suministrada desde la unidad exterior cuando se suministra de fábrica Si las unidades interior y exterior presentan fuentes de alimentación independientes cambie las conexiones tal y como se mues...

Страница 23: ... 2 AWG22 No polar AC 208 230 V DC12 V DC12 V DC12 V Los conmutadores DIP SW 5 2 y SW 5 3 sólo sur ten efecto cuando el conmutador DIP 5 1 K CON TROL está activado ON Cableado Cable n tamaño Rango del circuito 6 1 3 aplicación K control Están disponibles los siguientes patrones de conexión Los patrones de la fuente de alimentación de la unidad exterior varían en función del modelo Sistema 1 1 Coloq...

Страница 24: ...porte del mando a distancia en el lugar deseado atornillándolo con tacos 2 Inserte la parte inferior del mando en el soporte A Mando a distancia B Pared C Pantalla del mando D Receptor La señal alcanza aproximadamente hasta 7 metros 23ft en línea recta con un ángulo de desviación de hasta 45 a la izquierda y la derecha de la línea central del receptor 3 Preparación inicial Fig 6 6 1 Introduzca las...

Страница 25: ... botón TEMP C una vez para seleccionar 50 Apunte el mando a dis tancia hacia el receptor de la unidad interior y pulse el botón h A 2 Configuración del número de unidad Pulse el botónTEMP C y D para seleccionar el número de unidad 00 Apunte el mando a distancia hacia el receptor de la unidad interior y pulse el botón min B 3 Cómo seleccionar un modo Introduzca 04 para cambiar la tensión de aliment...

Страница 26: ...nción No utilice el aire acondicionado si la resistencia de aislamiento es inferior a 1 0 MΩ Ω Ω Ω Ω Resistencia del aislamiento 7 2 Prueba de funcionamiento Están disponibles los siguientes 3 métodos 7 2 1 Al usar el controlador remoto cableado Fig 7 1 1 Encienda el aparato por lo menos 12 horas antes de llevar a cabo la prueba de funcionamiento 2 Pulse el botón de prueba de funcionamiento TEST P...

Страница 27: ... 5 P5 Error de la bomba de drenaje 6 P6 Funcionamiento de seguridad por helada sobrecalentamiento 7 EE Error de comunicación entre unidades interior y exterior 8 P8 Error de temperatura del tubo 9 E4 Error de recepción de señal del controlador remoto 10 11 12 Fb Error del sistema de control de la unidad interior error de memoria etc Sin sonido No corresponde Controlador remoto inalámbrico Controla...

Страница 28: ...o anteriormente No se acepta ninguna señal procedente del controlador remoto La luz OPE parpadea Se emite un pitido breve Si no se puede activar la unidad adecuadamente después de haberse llevado a cabo la ejecución de prueba consulte la tabla siguiente para suprimir la causa Síntoma Causa Controlador remoto cableado LED 1 2 tarjeta de circuito impreso en unidad exterior PLEASE WAIT PLEASE WAIT Có...

Страница 29: ...l funcionamiento Si se detiene el aire acondicionado siga este pro cedimiento para que comience a funcionar COOL STABLE MODE HEAT STABLE MODE STABLE MODE CANCEL Funcionamiento de refrigeración estable Funcionamiento de calefacción estable Cancelación de operación estable Pantalla A Pulse el botón MODE para elegir el modo de funcionamiento Pulse el botón FILTER Esperando funcionamiento estable Pant...

Страница 30: ...îí 05 11 28 5 19 PM 1 ...

Страница 31: ...îí 05 11 28 5 19 PM 1 ...

Страница 32: ...to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U827H02 BG79U827H01_cover 06 5 18 10 00 2 J MITSUBISHI ELECTRIC CORPORATION ...

Отзывы: