53
F Check of compressor start failure
D Check of compressor winding
E Check of compressor operation time
●
Disconnect the connector between the compressor and intelligent power module/power module 1, and measure the resis-
tance between the compressor terminals.
<<Measurement point>>
At 3 points
BLK - WHT
BLK - RED
WHT - RED
<<Judgement>>
Refer to 10-4.
0[
Ω
] ················· Abnormal [short]
Infinite [
Ω
] ········ Abnormal [open]
NOTE
: Be sure to zero the ohmmeter before measurement.
Measure the resistance between the lead wires at 3 points.
After the compressor is heated with a drier,
does the compressor start? 1
Replace the compressor.
Compressor start failure. Activate pre-heat control.
(Refer to 9-2. "PRE-HEAT CONTROL SETTING")
No
Yes
Does the compressor run for 10 seconds or
more after it starts?
Check the refrigerant circuit.
Check the stop valve.
Yes
No
Con
fi
rm that 1~4 is normal.
• Electrical circuit check
1. Contact of the compressor connector
2. Output voltage of inverter P.C. board and balance of them (See 10-5. )
3. Direct current voltage between DB61(+) and (-) (
MUZ-GE09/12/1518,
MUY-GE09/12/1518)
/ JP715(+) and JP30(-) (
MUZ-GE24, MUY-GE24)
on
the inverter P.C. board
4. Voltage between outdoor terminal block S1-S2
1
Heat the compressor with
a drier for about 20 minutes.
Do not recover refrigerant
gas while heating.
Heating part
●
Connect the compressor and activate the inverter. Then measure
the time until the inverter stops due to over current.
<<Operation method>>
Start heating or cooling operation by pressing EMERGENCY
OPERATION switch on the indoor unit.
(TEST RUN OPERATION: Refer to 7-6.)
<<Measurement>>
Measure the time from the start of compressor to the stop of
compressor due to overcurrent.
Compressor starts
Abnormal
(IPM failure)
(Compressor winding short)
Abnormal
(Compressor lock out)
(Starting defect)
Abnormal
(Poor contact,)
(Inverter P.C. board defect)
(Disconnected connector)
Abnormal
(Refrigerant circuit defect)
(Closed valve)
Normal
0 second
1 second
2 seconds
10 seconds
10 minutes
<<Judgement>>
1
Intelligent power module:
MUZ-GE09/12/15/18/24NA
,
MUY-GE09/12/15/18/24NA
Power module:
Other models
OBH549F
Содержание Mr. Slim MUZ-GE15NA-1
Страница 5: ...5 MUZ GE24NA MUY GE24NA Piping Air outlet Drain outlet Air inlet back and side Drain hose OBH549F ...
Страница 13: ...13 MUZ GE09NA MUZ GE12NA 5 WIRING DIAGRAM MUZ GE09NA2 MUZ GE12NA2 OBH549F ...
Страница 14: ...14 MUZ GE09NAH MUZ GE12NAH MUZ GE09NAH2 MUZ GE12NAH2 OBH549F ...
Страница 15: ...15 MUY GE09NA MUY GE12NA MUY GE09NA2 MUY GE12NA2 OBH549F ...
Страница 16: ...16 MUZ GE15NA 1 MUZ GE15NA OBH549F ...
Страница 17: ...17 MUZ GE15NAH MUZ GE15NA2 OBH549F ...
Страница 18: ...18 MUY GE15NA MUZ GE15NAH2 OBH549F ...
Страница 19: ...19 MUY GE15NA 1 MUY GE15NA2 OBH549F ...
Страница 20: ...20 MUZ GE18NA MUZ GE18NA 1 OBH549F ...
Страница 21: ...21 MUZ GE18NAH MUY GE18NA OBH549F ...
Страница 22: ...22 MUY GE18NA 1 OBH549F ...
Страница 23: ...23 MUZ GE24NA OBH549F ...
Страница 24: ...24 MUY GE24NA OBH549F ...
Страница 73: ...73 OBH549F ...