background image

4-1. PURGING PROCEDURES AND LEAK TEST

1) Remove service port cap of stop valve on the side of the outdoor unit gas pipe. (The 

stop valve will not work in its initial state fresh out of the factory, totally closed with 
cap on.)

2) Connect gauge manifold valve and vacuum pump to service port of stop valve on 

the gas pipe side of the outdoor unit.

5-1. PUMPING DOWN

When relocating or disposing of the air conditioner, pump down the system following 
the procedure below so that no refrigerant is released into the atmosphere.
1) Connect the gauge manifold valve to the service port of the stop valve on the gas 

pipe side of the outdoor unit.

2) Fully close the stop valve on the liquid pipe side of the outdoor unit.
3) Close the stop valve on the gas pipe side of the outdoor unit almost completely so 

that it can be easily closed fully when the pressure gauge shows 0 MPa [Gauge] (0 
kgf/cm

2

).

4) Start the emergency COOL operation.
  To start the emergency operation in COOL mode, disconnect the power supply plug 

and/or turn off the breaker. After 15 seconds, connect the power supply plug and/or 
turn on the breaker, and then press the E.O. SW once. (The emergency COOL 
operation can be performed continuously for up to 30 minutes.)

5) Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure 

gauge shows 0.05 to 0 MPa [Gauge] (approx. 0.5 to 0 kgf/cm

2

).

6) Stop the emergency COOL operation.
 

Press the E.O. SW twice to stop the operation.

Stop valve for 
GAS

Stop valve cap
(Torque 19.6 to 
29.4 N•m, 200  
to 300 kgf▪cm)

Vacuum pump (or the vacuum 
pump with the function to 
prevent the back flow)

Gauge manifold valve 
(for R410A)

Compound pressure gauge 
(for R410A)

0.101 MPa  

(

760 mmHg)

Handle 
Low

Handle High

Adapter for pre-
venting the back 
flow

Charge hose 
(for R410A)

*Close

*Open

Hexagonal wrench

Precautions when using the control valve When attaching the control valve 

to the service port, valve core may 
deform or loosen if excess pressure 
is applied. This may cause gas leak.

Service port

Charge hose 

Body

Close

Open

Control valve

A

When attaching the control valve to 
the service port, make sure that the 
valve core is in closed position, and 
then tighten part A. Do not tighten 
part A or turn the body when valve 
core is in open position.

Service port cap
(Torque 13.7 to 
17.7 N•m, 140 to 
180 kgf•cm)

*4 to 5 turns

3) Run the vacuum pump. (Vacuumize for more than 15 minutes.)
4) Check the vacuum with gauge manifold valve, then close gauge manifold valve, and 

stop the vacuum pump.

5) Leave as it is for one or two minutes. Make sure pointer gauge manifold valve re-

mains in the same position. Confirm that pressure gauge shows –0.101 MPa [Gauge] 
(–760 mmHg).

6) Remove gauge manifold valve quickly from service port of stop valve.
7) After refrigerant pipes are connected and evacuated, fully open all stop valves on 

both sides of gas pipe and liquid pipe. Operating without fully opening lowers the 
performance and this causes trouble.

8) Refer to 1-3., and charge the prescribed amount of refrigerant if needed. Be sure to 

charge slowly with liquid refrigerant. Otherwise, composition of the refrigerant in the 
system may be changed and affect performance of the air conditioner.

9) Tighten cap of service port to obtain the initial status.
10) Leak test

Stop valve 
for LIQUID

4.  PURGING PROCEDURES, LEAK TEST, AND TEST RUN

Pressure gauge
(for R410A)

5. PUMPING DOWN

4-4. EXPLANATION TO THE USER

•  Using the OPERATING INSTRUCTIONS, explain to the user how to use the air condi-

tioner (how to use the remote controller, how to remove the air filters, how to remove or 
put the remote controller in the remote controller holder, how to clean, precautions for 
operation, etc.)

•  Recommend the user to read the OPERATING INSTRUCTIONS carefully.

Emergency  
operation switch
(E.O. SW)

Caution:

•  After test run or remote signal reception check, turn off the unit with the E.O. SW or the 

remote controller before turning off the power supply. Not doing so will cause the unit 
to start operation automatically when power supply is resumed.

To the user

•  After installing the unit, make sure to explain the user about auto restart function. 
•  If auto restart function is unnecessary, it can be deactivated. Consult the service repre-

sentative to deactivate the function. Refer to the service manual for details.

4-3. AUTO RESTART FUNCTION

This product is equipped with an auto restart function. When the power supply is stopped 
during operation, such as during blackouts, the function automatically starts operation in the 
previous setting once the power supply is resumed. (Refer to the operating instructions for 
details.) 

4-2. TEST RUN

Make sure the following is done.

• The area around the damper is free of any objects, and the movement of the damper is not 

blocked.

• Panel is installed correctly.
• Indoor and outdoor units are installed 

correctly, and power is supplied.

1) Press the E.O. SW once for COOL, 

and twice for HEAT operation. Test 
run will be performed for 30 minutes. If 
the left lamp of the operation indicator 
blinks every 0.5 seconds, inspect the 
indoor/outdoor unit connecting wire (A) 
for mis-wiring. After the test run, emer-
gency mode (set temperature 24ºC) will 
start.

2) To stop operation, press the E.O. SW several times until all LED lamps turn off. Refer to 

operating instructions for details. 

Checking the remote (infrared) signal reception

Press the ON/OFF button on the remote controller (12) and check that an electronic sound 
is heard from the indoor unit. Press the ON/OFF button again to turn the air conditioner off.
•  Once the compressor stops, the restart preventive device operates so the compressor 

will not operate for 3 minutes to protect the air conditioner.

3-3. PIPE CONNECTION

•  Fasten flare nut with a torque wrench as specified in the table.
•  When fastened too tight, flare nut may break after a long period and cause refrigerant 

leakage.

Indoor unit connection

Connect both liquid and gas pipings to indoor unit.
•  Apply a thin coat of refrigeration oil (J) on the seat surface of pipe.
•  For connection, first align the center, then tighten the first 3 to 4 turns of flare nut.
•  Use tightening torque table below as a guideline for indoor unit side union joint sec-

tion, and tighten using two wrenches. Excessive tightening 
damages the flare section.

Outdoor unit connection

Connect pipes to stop valve pipe joint of the outdoor unit in 
the same manner applied for indoor unit.
•  For tightening, use a torque wrench or spanner and use 

the same tightening torque applied for indoor unit.

3-4. INSULATION AND TAPING

1) Cover piping joints with pipe cover.
2) For outdoor unit side, surely insulate every piping including valves.
3) Using piping tape (G), apply taping starting from the entry of outdoor unit.

•  Stop the end of piping tape (G) with tape (with adhesive agent attached).
•  When piping have to be arranged through above ceiling, closet or where the 

temperature and humidity are high, wind additional commercially sold insulation to 
prevent condensation.

 WARNING

When installing the unit, securely connect the refrigerant pipes before starting 
the compressor.

When pumping down the refrigerant, stop the compressor before disconnecting 
the refrigerant pipes. The compressor may burst if air etc. get into it.

 WARNING

Содержание MFZ-FB50VA

Страница 1: ...ompressor If the compressor is started before the refrigerant pipes are connected and when the stop valve is open air could be drawn in and the pressure in the refrigeration cycle could be come abnormally high This could cause the pipes to burst or injury N Fasten a flare nut with a torque wrench as specified in this manual If fastened too tight a flare nut may break after a long period and cause ref...

Страница 2: ...inutes and pump down before removing the old air conditioner Remake flare accord ing to the dimension for new refrigerant 2 INDOOR UNIT INSTALLATION Note Place indoor outdoor unit connecting wire A and power supply cord K at least 1 m away from the TV antenna wire Air inlet Air outlet Outdoor unit installation 4 10 mm 21 mm slot 840 mm 500 mm 169 mm 40 mm 392 mm 330 mm 360 mm IMPORTANT NOTES To com...

Страница 3: ...If the horizontal bars will block the lower air outlet use a stand etc to adjust the height of the indoor unit If the upper or lower air outlet is blocked the air conditioner will not be able to cool or warm the room well Do not block the receiver with the grating Otherwise the grating will interfere with the remote controller signal and significantly reduce the distance and area angle from which t...

Страница 4: ... pipes Make sure that the drain hose is not routed upward and that there are no waves in the hose Do not pull the hose when applying the tape Route the piping so that it does not project past the rear of the indoor unit Refer to the figure to the right Connecting Pipe Installation Install the connecting pipes so that the piping can move slightly to the front back left and right Piping tape Drain ho...

Страница 5: ...75 ø15 88 5 8 29 73 5 to 78 4 750 to 800 Smooth all around Even length all around Inside is shin ing without any scratches Flare nut Die Fig 5 Fig 6 Copper pipe Do not make drain piping as shown below Accumulated drain water Air Waving Water leakage Do not raise Water leakage Water leakage Tip of drain hose dipped in water Ditch At least 50 mm gap Downward slope Drain hose Soft hose I D 15 mm Drai...

Страница 6: ...remote controller how to remove the air filters how to remove or put the remote controller in the remote controller holder how to clean precautions for operation etc Recommend the user to read the OPERATING INSTRUCTIONS carefully Emergency operation switch E O SW Caution After test run or remote signal reception check turn off the unit with the E O SW or the remote controller before turning off the...

Страница 7: ... to the indoor control board of an air conditioner with a connect ing cable Cutting or extending the connecting cable of the interface results in defects in connecting Do not bundle the connecting cable together with power supply cord indoor outdoor connecting wire and or earth wire Keep as much distance as pos sible between the connecting cable and those wires The thin part of the connecting cabl...

Страница 8: ...HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Отзывы: