3 SIGNALS AND WIRING
3.3 Explanation of power supply system
29
3
*1 If using the ferrule manufactured by DAIDO SOLDERLESS TERMINAL MFG., leave the stripped wire end 8.5 mm ± 0.5 mm from the
ferrule tip and insulate the wire using a heat shrink tube with a length of 14 mm or more.
*2 If crimping two wires into the ferrule, align the wires so that pressure can be applied in the crimping direction as shown below.
Insert the ferrule into the connector with the two crimped wires aligned vertically to the connector as shown below. Do not rotate the
ferrule in the pitch direction.
■
Inserting wire
Insert only one wire or ferrule into each wire insertion hole on each power connector.
Insert the open tool as follows and push it down to open the spring.
While the open tool is pushed down, insert the stripped wire into the wire insertion hole. Check the wire insertion depth so that
the wire insulator is not caught by the spring and that the conductive part of the stripped wire is not exposed.
Release the open tool to fix the wire. Pull the wire lightly to confirm that the wire is surely connected. In addition, confirm that
the ends of the core wires do not stick out of the connector.
8.5 mm ± 0.5 mm
14 mm or longer
Where a heat shrink tube is used
Crimping direction
Connector
Connector
Sleeve
Sleeve
Wire
Wire
(1) Push down the open tool.
(2) Insert the wire.