8 OPTIONS AND PERIPHERAL EQUIPMENT
8.2 AC reactor
67
8
8.2
AC reactor
Always connect one AC reactor to one power regeneration converter unit.
The AC reactor generates heat of 100
higher than the ambient temperature. Fully consider heat dissipation, installation
position, wires used, etc., before installing the AC reactor.
Magnetism generated from the AC reactor may affect other devices. Leave a clearance of 100 mm or more around wires so
that they do not contact the AC reactor.
Specifications
Model
MR-AL-55K4-L
Rated capacity [kW]
55
Rated voltage
380 V AC to 480 V AC (power fluctuation ratio: within ±10%)
Rated current [A]
106
Frequency
50 Hz/60 Hz (frequency fluctuation: within ±3%)
Environment
Ambient
temperature
Operation
0
to 55
(non-freezing)
Storage
-20
to 65
(non-freezing)
Ambient
humidity
Operation
5 %RH to 90 %RH (non-condensing)
Storage
Ambience
Indoors (no direct sunlight), no corrosive gas, inflammable gas, oil mist, dust, or conductive particle
Altitude
2000 m or less above sea level
Vibration resistance
5.9 m/s
2
or less
Loss [W]
330
Mass [kg]
56