Specifications
2.1
General Specifications
E
CAUTION:
Please operate the modules of the MELSEC ST Series in the listed conditions only.
If the modules are used under other conditions, electric shock, fire, malfunction, dam-
ages or deterioration may be caused.
햲
This indicates the section of the power supply to which the equipment is assumed to be
connected between the public electrical power distribution network and the machinery
within premises. Category II applies to equipment for which electrical power is supplied
from fixed facilities. The surge voltage withstand level for up to the rated voltage of 300 V is
2500 V.
햳
This index indicates the degree to which conductive material is generated in the environ-
ment where the equipment is used. Pollution level 2 is when only non-conductive pollution
occurs but temporary conductivity may be produced due to condensation.
MELSEC ST Series
11
Specifications
Item
Specifications
Operating ambient
temperature
0 to +55 °C
Storage ambient
temperature
−
25 to +75 °C
Ambient humidity for opera-
tion and storage
5 to 95 %, relative humidity, non-condensing
Vibration resistance
Conforms to
JISB3501
and
IEC61131-2
Intermittent Vibration
Frequency
Acceleration
Amplitude
(half)
Sweep count for
X, Y, Z
10 to 57 Hz
—
0.075 mm
10 times
(80 minutes in
each direction)
57 to 150 Hz
9.8 m/s
2
(1 g)
—
Continuous Vibration
10 to 57 Hz
—
0.035 mm
57 to 150 Hz
9.8 m/s
2
(1 g)
—
Shock resistance
Conforms to JIS B3501 and IEC61131-2: 15 g, 3 times in each direction X, Y und Z
Operating environment
No dust, soot, corrosive or conductive dust, corrosive or flammable gas
Operating altitude
max. 2000 m above MSL (Main Sea Level)
(Do not use or store the PLC under pressure higher than the atmospheric pressure
at MSL (0 m). Doing so can cause malfunction. When using the PLC under pressure,
please contact your local representative.)
Installation location
Inside control panel
Overvoltage category
���
II max.
Pollution level
���
2 max.