6 - 66 6 - 66
6 IEC FUNCTIONS
Argument Type
ST Program
Conversion Result
Used Instruction
DINT
b_result := LT_E( b_select,
di_data1, di_data2, di_data3,
b_data1 );
LDD< di_data1 di_data2
ANDD< di_data2 di_data3
OUT
M8191
LD
b_select
AND
M8191
SET
b_data1
LD
b_select
ANI
M8191
RST
b_data1
LD
b_select
OUT
b_result
LDD<, ANDD<,OUT,
LD,AND,SET,ANI,
RST
BOOL
b_result := LT_E( b_select,
X10, X11, X12, M20 );
LDI
X10
AND
X11
LDI
X11
AND
X12
ANB
OUT
M8191
LD
b_select
AND
M8191
SET
M20
LD
b_select
ANI
M8191
RST
M20
LD
b_select
OUT
b_result
LDI,AND,ANB,OUT,
LD,SET,ANI,RST
STRING
b_result := LT_E( b_select,
s_ary1, s_ary2, b_data1 );
LD$<
s_ary1 s_ary2
OUT
M8191
LD
b_select
AND
M8191
SET
b_data1
LD
b_select
ANI
M8191
RST
b_data1
LD
b_select
OUT
b_result
LD$<,OUT,LD,AND,
SET,ANI,RST
For the usable data type, refer to "3.2.2 About ANY type".