6 - 64 6 - 64
6 IEC FUNCTIONS
Argument Type
ST Program
Conversion Result
Used Instruction
DINT
b_result := LE_E( b_select,
di_data1, di_data2, di_data3,
b_data1 );
LDD<= di_data1 di_data2
ANDD<= di_data2 di_data3
OUT
M8191
LD
b_select
AND
M8191
SET
b_data1
LD
b_select
ANI
M8191
RST
b_data1
LD
b_select
OUT
b_result
LDD<=, ANDD<=,
OUT,LD,AND,SET,
ANI,RST
BOOL
b_result := LE_E( b_select,
X10, X11, X12, M20 );
LDI
X10
OR
X11
LDI
X11
OR
X12
ANB
OUT
M8191
LD
b_select
AND
M8191
SET
M20
LD
b_select
ANI
M8191
RST
M20
LD
b_select
OUT
b_result
LDI,OR,ANB,OUT,
AND,SET,ANI,RST
STRING
b_result := LE_E( b_select,
s_ary1, s_ary2, b_data1 );
LD$<= s_ary1 s_ary2
OUT
M8191
LD
b_select
AND
M8191
SET
b_data1
LD
b_select
ANI
M8191
RST
b_data1
LD
b_select
OUT
b_result
LD$<=,OUT,LD,
AND,SET,ANI,RST
For the usable data type, refer to "3.2.2 About ANY type".