38
1 FUNCTIONS
1.2 Output Function
Clearing the number of output ON times
The number of output ON times can be cleared with 'Number of output ON times value clear request' (Un\G3840).
Each bit of 'Number of output ON times value clear request' (Un\G3840) corresponds to each output.
When the bit corresponding to the output to be cleared is changed from 0 (Not requested) to 1 (Requested), the value of
'Number of output ON times' (Un\G3136 to Un\G3167) is cleared and 1 (Completed) is stored in 'Number of output ON times
value clear completed' (Un\G3168).
Even if 1 (Completed) is stored in 'Number of output ON times value clear completed' (Un\G3168), the bit of 'Number of output
ON times value clear request' (Un\G3840) is not automatically changed to 0 (Not requested). Set 0 (Not requested) in
'Number of output ON times value clear request' (Un\G3840) with a program.
When 0 (Not requested) is stored in 'Number of output ON times value clear request' (Un\G3840), the bit of 'Number of output
ON times value clear completed' (Un\G3168) is changed to 0 (Not completed).
For each bit of 'Number of output ON times value clear request' (Un\G3840) and the output to be cleared, refer to the
following.
Page 113 Number of output ON times value clear request
Setting procedure
Set the following items from "Application setting".
• "Output ON number count function enable/disable" (
Page 103 Number of output ON times integration function enable/
• "Number of output ON times alarm detect setting" (
Page 104 Number of output ON times alarm detection setting)
• "Number of output ON times alarm detect count setting" (
Page 104 Number of output ON times alarm detection count
[Navigation window]
[Parameter]
[Module Information]
Target module
[Module Parameter]
[Application
setting]
0
100
0
1
0
1
0
0
1
'Number of output ON times
value clear completed' (Un\G3168)
'Number of output ON times'
(Un\G3136 to Un\G3167)
'Number of output ON times
value clear request' (Un\G3840)