104
APPX
Appendix 3 Buffer Memory
Number of output ON times alarm detection setting
Set whether to detect an alarm for the number of output ON times for each output.
■
Buffer memory address
The following table shows the buffer memory address of this area.
■
Enabling the setting
Turn on and off 'Operating condition setting request' (Y12) to enable the setting.
■
Default value
The default value is set to 0 (Not detect) for all the outputs.
Number of output ON times alarm detection count setting
Set the number of output ON times alarm detection count for each output.
■
Buffer memory address
The following table shows the buffer memory address of this area.
■
Setting range
• The available range is 1 to 4294967295.
• The number of output ON times alarm detection count setting error (error code: 1A6
H) occurs in the output terminal
where a value out of the setting range has been set.
indicates the number of an I/O terminal in which the error has
occurred. (
= 0H to FH)
■
Enabling the setting
Turn on and off 'Operating condition setting request' (Y12) to enable the setting.
■
Default value
The default value is set to 1 for all the inputs.
(1) 0: Not detect, 1: Detect
Buffer memory name
Y0 to YF
Number of output ON times alarm detection
setting
1908
Buffer memory name
Y00
Y01
Y02
Y03
Y04
Y05
Y06
Y07
Y08
Y09
Y0A
Y0B
Y0C
Y0D
Y0E
Y0F
Number of output ON times
alarm detection count setting
1912
1913
1914
1915
1916
1917
1918
1919
1920
1921
1922
1923
1924
1925
1926
1927
1928
1929
1930
1931
1932
1933
1934
1935
1936
1937
1938
1939
1940
1941
1942
1943
Y00
(1)
Y01
Y02
Y03
Y04
Y05
Y06
Y07
Y08
Y09
Y0A
Y0B
Y0C
Y0D
Y0E
Y0F
b0
b1
b2
b3
b4
b5
b6
b7
b8
b9
b10
b11
b12
b13
b14
b15
Содержание MELSEC iQ-RX40NC6B
Страница 1: ...MELSEC iQ R I O Module With Diagnostic Functions User s Manual Application RX40NC6B RY40PT5B ...
Страница 2: ......
Страница 125: ...4 OVERVIEW 123 4 MEMO ...
Страница 191: ...12 MAINTENANCE AND INSPECTION 189 12 MEMO ...
Страница 227: ......