12 DATA USED FOR POSITIONING CONTROL
12.3 Basic Setting
385
12
[Pr.6] Rotation direction setting
Set the relation of the positioning direction (increment direction or decrement direction of [Md.20] Current feed value) and the
pulse output. For the relation of "Forward run pulse output, Reverse run pulse output" and "CW/A phase/PULSE signal, CCW/
B phase/SIGN signal", refer to the following.
Page 383 [Pr.5] Pulse output mode
Ex.
The following figure shows the pulse outputs of when [Pr.5] Pulse output mode is set to the CW/CCW mode and the
positioning of current feed value increment and of current feed value decrement is executed.
When this area is changed from 0 to 1, check if the upper limit switch and lower limit switch operate properly
with JOG operation. If any malfunction is identified, check and correct the wiring.
■
Buffer memory address
The following table shows the buffer memory address of this area.
■
Default value
The default value is 0: Current value increment with forward run pulse output for all the axes.
Rotation direction setting
Setting value
Current value increment with forward run pulse output
0
Current value increment with reverse run pulse output
1
Buffer memory name
Axis 1
Axis 2
Axis 3
Axis 4
[Pr.6] Rotation direction setting
5
155
305
455
0→1→2→3→4
4→3→2→1→0
4
0
cw
ccw
cw
ccw
0
Md.20
Current feed
value
Positioning of
current feed value
increment
Positioning of
current feed value
decrement
Forward run
pulse output
Reverse run
pulse output
Reverse run
pulse output
Forward run
pulse output
When "0: Current value increases by forward run pulse output" is set
When "1: Current value increases by reverse run pulse output" is set
Содержание MELSEC iQ-R RD75P4
Страница 1: ...MELSEC iQ R Positioning Module User s Manual Application RD75P2 RD75P4 RD75D2 RD75D4 ...
Страница 2: ......
Страница 13: ...11 MEMO ...
Страница 19: ...17 CONTENTS INDEX 588 REVISIONS 592 WARRANTY 593 TRADEMARKS 594 ...
Страница 498: ...496 13 PROGRAMMING 13 2 List of Labels Used ...
Страница 503: ...13 PROGRAMMING 13 4 Program Example 501 13 ...
Страница 511: ...13 PROGRAMMING 13 4 Program Example 509 13 Torque change program Step operation program Skip program ...
Страница 512: ...510 13 PROGRAMMING 13 4 Program Example Teaching program Continuous operation interrupt program ...
Страница 513: ...13 PROGRAMMING 13 4 Program Example 511 13 Target position change program Absolute position restoration program ...
Страница 514: ...512 13 PROGRAMMING 13 4 Program Example Restart program Parameter data initialization program ...
Страница 515: ...13 PROGRAMMING 13 4 Program Example 513 13 Flash ROM write program Error reset program ...
Страница 516: ...514 13 PROGRAMMING 13 4 Program Example Stop program ...
Страница 565: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 563 A ...
Страница 568: ...566 APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted Common program ...
Страница 584: ...582 APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted Restart program ...
Страница 587: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 585 A Stop program ...
Страница 597: ......