Appendix 3 Troubleshooting by Symptom
Appendix 3
Troubleshooting by Symptom
If any function of the CPU module does not operate as designed, perform troubleshooting by checking the following items. If
the ERROR LED or USER LED is on or flashing, eliminate the error cause using the engineering tool.
When the POWER LED of the power supply module turns off
For troubleshooting, refer to the following:
MELSEC iQ-R Module Configuration Manual
When the READY LED of the CPU module turns off
Check the following:
If the READY LED of the CPU module does not turn on even after the items above are checked and the actions are taken, the
possible cause is a hardware failure of the power supply module. Please consult your local Mitsubishi representative.
Check item
Action
Check if the CPU module is mounted on the main base unit properly.
Remove the CPU module from the main base unit, and mount it back on the
main base unit.
Check if the READY LED of another module is on.
A major error has occurred in the CPU module. Replace the CPU module.
Check if the READY LED turns on when the power supply module is replaced
and the power is restored to the system.
(Check the LED status after the power supply module on the extension base
unit is also replaced.)
An error has occurred in the power supply module(s) before the replacement.
Replace the power supply module.
Check if the READY LED does not turn on even after the power supply
module is replaced and the power is restored to the system.
(Check the LED status after the power supply module on the extension base
unit is also replaced.)
An error has occurred in a module other than the power supply module.
Repeatedly supply power to the system, returning the modules back to the
system one by one.
The last module mounted immediately before the READY LED turned off has
been failed. Replace the module.
Check if the system was powered on immediately after power-off.
Wait for five seconds or longer after power-off and power on the system again.
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......