6 WIRING
6.7 Examples of Wiring for Various Uses
119
6
Interruption
Examples of wiring for when the input interruption function is used are shown below.
The same wiring is used for the pulse catch and pulse width measurement functions.
When capturing pulses of a response frequency of 50 to 100 kHz, refer to
Page 94 In the case of capturing high-speed
pulses.
For details on the input interruption function, pulse catch function and pulse width measurement function, refer to
MELSEC iQ-F FX5 User's Manual (Application).
Example of wiring
■
When 24 V DC service power supply is used
■
When 24 V DC external power supply is used
*1 The grounding resistance should be 100
Ω
or less.
1.5 k
In the case of sink wiring
S/S
L
N
24V
Class D grounding
*1
Fuse
FX5UJ-40MT/ES
0V
X0
3-wire type
1.5 k
In the case of source wiring
FX5UJ-40MT/ESS
S/S
L
N
24V
Class D grounding
*1
Fuse
0V
X0
3-wire type
1.5k
FX5UJ-40MT/ES
In the case of sink wiring
S/S
L
N
24V
Class D grounding
*1
Fuse
24 V DC
0V
X0
3-wire type
1.5k
FX5UJ-40MT/ESS
In the case of source wiring
S/S
L
N
24V
Class D grounding
*1
Fuse
24 V DC
0V
X0