2. FAULT DIAGNOSIS
2.2 Troubleshooting
II
-4
2.2 Troubleshooting
2.2.1 Confirmation of trouble state
Confirm "when", "when doing what", and "what kind of" trouble occurred.
(1) When?
What time did the trouble occur?
(2) When
doing
what?
What was the NC operation mode?
(3) What kind of trouble?
• What was displayed on the setting display unit's Alarm Diagnosis screen?
Display the Alarm Diagnosis screen, and check the alarm details.
• What was displayed for the machine sequence alarm?
• Is the CRT and LCD screen normal?
(4) How
frequently?
• When did the trouble occur? What was the frequency? (Does it occur when other machines are
operating?) If the trouble occurs infrequently or if it occurs during the operation of another
machine, there may be an error in the power voltage or the trouble may be caused by noise, etc.
Check whether the power voltage is normal (does it drop momentarily when other machines are
operating?), and whether noise measures have been taken.
• Does the trouble occur during a specific mode?
• Does the trouble occur when the overhead crane is operating?
• What is the frequency in the same workpiece?
• Check whether the same trouble can be repeated during the same operation.
• Check whether the same trouble occurs when the conditions are changed.
(Try changing the override, program details, and operation procedures, etc.)
• What is the ambient temperature?
(Was there a sudden change in the temperature?
• Is there any contact defect or insulation defect in the cables?
(Has any oil or cutting water splattered onto the cables?)