103
Specifications
5. Specifications of MODBUS
®
TCP Communication
Item
Specifications
Interface
1 port (10BASE-T/100BASE-TX)
Transmission method
Base band
Number of cascade connection stages *1
Max. 4 stages (10BASE-T), Max. 2 stages (100BASE-TX)
Maximum node-to-node distance
200m (656.16ft.)
Maximum segment length *2
100m (328.08ft.)
Connector applicable for external wiring
RJ45
Cable
10BASE-T
Cable compliant with the IEEE802.3 10BASE-T Standard
(unshielded twisted pair cable (UTP cable), Category 3 or more)
100BASE-TX
Cable compliant with the IEEE802.3 100BASE-TX Standard
(shielded twisted pair cable (STP cable), Category 5 or more)
Protocol
MODBUS TCP (Port number 502)
Number of simultaneously connection
Max. 4 connection
Functions supported
Autonegotiation (10BASE-T/100BASE-TX automatically detected)
Auto MDIX function (straight/crossover cable automatically detected)
*1.
This is the maximum number of cascade connection stages when a repeater hub is used.
For the maximum number of cascade connection stages, contact to the manufacturer for the switching hub used.
*2.
Length between a hub and a node.
About Programming
In addition to this manual, read the following documents too.
Electronic Multi-Measuring Instrument ME Series MODBUS® Interface specifications ..................................... LSPM-0075
6. Specifications of Logging
Item
Specifications
Logging mode
Auto overwriting updating
Type of
logging data
(*1)
Detailed data
Memorize measured data in the specified “Detailed data logging cycle” (1 minute,
5 minutes, 10 minutes, 15 minutes or 30 minutes).
Data is output as detailed data file.
One-hour data
Memorize measured data in one-hour cycle.
Data is output as One-hour data file and One-day data file
The number of
logging items
Detailed data
Up to 6 items
One-hour data
Up to 6 items
Internal
memory
logging period
Detailed data
Logging cycle
Logging period
1minute
2 days
5minute
10 days
10minute
20 days
15minute
30 days
30minute
60 days
One-hour data
400 days (About 13 months)
Logging period with SD memory card
(2GB) *2
10 years or longer
System log data
1200 records
Output format of logging data and
system log data
CSV format (ASCII)
Compensation for power failure
Lithium battery (Embedded in ME-0000BU-SS96)
Total time of compensation is 5 year (average daily temperature is less than +35°C).
(Lifetime expectancy of lithium battery is 10 year) (average daily temperature is less
than +35°C).
It is impossible for customer to exchange the battery. Please consider renewal.
Setting values
(Logging ID, Logging items,
Detailed data logging cycle)
Memorized in FRAM (nonvolatile memory)
The data is memorized during power failure.
Logging data,
System log data
Memorized in SRAM (volatile memory)
Data is erased if power failure occurs under low battery voltage condition (BAT.LED
turns on).
Clock time operation
Clock time operation is stopped if power failure occurs under low battery voltage
condition (BAT.LED turns on). After power recovery, timing is started from Jan 1, 2016
00:00:00.
Clock accuracy
Within ±1 minute per month (at 25
℃
)
Memory media for data output *3
SD memory card (SD, SDHC)
Optional part
SD memory card (EMU4-SD2GB) *3 *4
*1.
Energy data (Wh,varh,VAh) is measuring data in ME96SS. These are not difference value calculated by logging cycle.
*2.
It is the period until capacity of 2GB SD memory card is filled in always-on connection. Data amount depends on the number
of characters. It is the logging period when data is output in maximum volume.
*3. Make sure to use the SD memory card manufactured by Mitsubishi Electric Corporation (Model EMU4-SD2GB). Using the
other types of the SD memory card may cause the trouble such as data destruction of the memory card or system failure.
*4. For purchase of optional parts, contact the shop you bought this product.
In addition to this manual, read the following documents too.
ME-0000BU-SS96:Logging specifications .................................................................................................... LSPM-0092
Содержание ME96SSRA-MB
Страница 88: ...87 Installation 1 Dimensions ME96SSRA MB Optional Plug in Module ME 4210 SS96 ME 0040C SS96 ME 0052 SS96 ...
Страница 89: ...88 Installation 1 Dimensions Optional Plug in Module ME 0000MT SS96 Optional Plug in Module ME 0000BU SS96 ...
Страница 98: ...97 Installation 4 Wiring Diagram Optional Plug in Module ME 0000MT SS96 Optional Plug in Module ME 0000BU SS96 ...