5
● The air coverage is the figure up to the
position where the air speed is 1 ft./s.,
when air is blown out horizontally from
the unit properly at the High speed posi-
tion.
The coverage should be used only as a
general guideline since it varies accord-
ing to the size of the room and furniture
arranged inside the room.
3-2. OUTLET AIR SPEED AND COVERAGE
Multi connection
Model
Mode
Function
Airflow
(CFM)
Air speed
(ft./s.)
Coverage (ft.)
MLZ-KP09NA
MLZ-KP09NA2
HEAT
Dry
311
13.0
20.7
COOL
Dry
325
13.6
21.7
Wet
—
—
—
MLZ-KP12NA
MLZ-KP12NA2
HEAT
Dry
332
13.9
22.1
COOL
Dry
350
14.6
23.3
Wet
—
—
—
MLZ-KP18NA
MLZ-KP18NA2
HEAT
Dry
403
16.9
26.7
COOL
Dry
417
17.5
27.6
Wet
—
—
—
(2) OPERATION
*The operating range of the outdoor unit depends on the connected outdoor unit.
Mode
Condition
Intake air temperature (°F)
Indoor
Outdoor
DB
WB
DB
WB
Cooling
Standard temperature
80
67
95
—
Maximum temperature
90
73
115
—
Minimum temperature
67
57
14
—
Maximum humidity
78%
—
Heating
Standard temperature
70
60
47
43
Maximum temperature
80
67
75
65
Minimum temperature
70
60
-13
-14
3-1. OPERATING RANGE
(1) POWER SUPPLY
Rated voltage
Guaranteed voltage (V)
Indoor unit
208/230 V
1 phase
60 Hz
Min. 187
208
230
Max. 253
OBH802B