35
VG79D920H01
en
11-2. Function setting
Make function settings by setting the dipswitches SW4, SW6, and SWP1 on the main board.
Write down the switch settings on the electrical wiring diagram label on the control box front panel for future reference
when the control box needs to be replaced.
・
Take the following steps to make settings.
①
Set the 10th bit of SW6 to ON.
②
Set SW4. (The setting item No. will be displayed on LED1.)
③
Press SWP1 for two seconds or longer to change the settings. (The settings can be checked on LED3.)
・
Make various function settings by setting SW6, referring to the table below.
Setting content
Setting
Switch setting timing
OFF
ON
SW6-1
–
–
–
–
SW6-2
–
–
–
–
SW6-3
–
–
–
–
SW6-4
Static pressure setting
Standard static pressure
High static pressure
Before being energized
SW6-5
High static pressure setting
60 Pa
30 Pa
Before being energized
SW6-6
–
–
–
–
SW6-7
Low-noise mode selection
Performance priority
Low-noise priority
Any time after being energized
SW6-8
Selection of Low-noise or Demand
Low-noise (Night)
Demand
Before being energized
SW6-9
System configuration
Two-outdoor-unit system
Single-outdoor-unit
system
Before being energized
SW6-10
Selection of Diagnostic display or
Function detail setting
Diagnostic display
Function detail setting
Any time after being energized
* Do not change the factory settings of SW5-3 through SW5-8.
* Unless otherwise specified, leave the switch to OFF where indicated by "–," which may be set to OFF for a reason.
11-3. Operation characteristics in relation to the refrigerant charge
It is important to have a clear understanding of the characteristics of refrigerant and the operation characteristics of air
conditioners before attempting to adjust the refrigerant charge in a given system.
・
During cooling operation, the amount of refrigerant in the accumulator is the smallest when all indoor units are in
operation.
・
Refrigerant undercharge creates a tendency for the discharge temperature to rise.
・
Changing the amount of refrigerant in the system while there is refrigerant in the accumulator has little effect on the
discharge temperature.
・
The higher the high pressure level, the more likely it is for the discharge temperature to rise.
・
The lower the low pressure level, the more likely it is for the discharge temperature to rise.
・
When the amount of refrigerant in the system is adequate, the compressor shell temperature is 10 to 60ºC (50 to
140ºF) higher than the low-pressure saturation temperature. If the temperature difference between the compressor
shell temperature and low-pressure saturation temperature is 5ºC (41ºF) or less, refrigerant overcharge is
suspected.
11-4. Operation check
The following symptoms are normal and do not indicate a problem.
Events
Cause
Immediately after startup, the indoor unit
emits the sound of refrigerant flowing.
Unstable flow of the refrigerant produces a sound. This is temporary and does not
imply a problem.