8
VG79D920H01
2. About the product
・
The outdoor unit described in this manual is air-conditioning equipment that is designed to be operated in the
cooling mode only for IT equipment.
・
This unit uses R410A refrigerant.
3. Combination of outdoor units
Configuration
Combination of outdoor units
Single-outdoor-unit system
m-MOCU-G02-050
-
Two-outdoor-unit system
m-MOCU-G02-050
m-MOCU-G02-050
* "Twinning Kit" is required to connect combination units on site.
4. Specifications
Configuration
Single-outdoor-unit system
Two-outdoor-unit system
Sound level (50/60 Hz)
65.0 dB <A>
68.0 dB <A>
External static pressure
0 Pa*
2
Indoor unit
Total capacity
50% to 150%*
1
Quantity
1 to 10
Operation temperature
Cooling: -15°CDB to 45°CDB
*1 The maximum total capacity of indoor units operating simultaneously is 100%.
*2 To enable the high static pressure setting, set the dipswitch on the main board as follows.
SW6-4: ON
SW6-5: OFF (60 Pa) or ON (30 Pa)
5. Package contents
The table below lists all the parts and their quantities included in the package.
①
②
③
Connecting pipe
(Liquid side)
Connecting elbow
(Gas side)
Tie band
ID ø15.88 mm (ø5/8 in)
OD ø15.88 mm (ø5/8 in)
ID ø28.58 mm (ø1-1/8 in)
OD ø28.58 mm (ø1-1/8 in)
P500
1
1
2
OD ø15.88
ID ø15.88
OD ø28.58
ID ø28.58