4. Electrical Work

 

WARNING

-  Use a dedicated circuit for the equipment to be connected, and use 

the voltage and breaker appropriate for the connected load.

-  Connected equipment should be used within the rated voltage and 

control capacity range.

-  All electrical work must be performed by a licensed technician, 

according to local regulations and the instructions given in the 
Installation manual.

- Use the specified cables for wiring and connect them securely. 

Hold the cables so as not to apply external force of the cables to 

the Terminal block of this product.

Lossnay operation,malfunction,By-pass ventilation,supply fan 

operation,exhaust fan operation,Pre-heater signal, and supply fan 

monitor output with delay operation (for after heater) signals can be 

output from the TM3 terminal of the Lossnay unit control board and the 

TM300 terminal of the PZ-4GS-E.

Connection terminal

PZ-62DR-E

Function No.

Output*

Lossnay unit

TM3 

9

 and 

0

12

Operation monitor

PZ-4GS-E

(TM300)

COM-OUT1

13

Malfunction monitor

COM-OUT2

14

By-pass monitor

COM-OUT3

15

Supply fan operation monitor

COM-OUT4

16

Exhaust fan operation 

monitor

* Factory settings of Lossnay LGH-RVS series. The setting may differ 

according to the type of Lossnay series. Be sure to refer each Lossnay 

unit installation manual for detail setting.

The output signals from each terminal can be changed arbitrarily from 

PZ-62DR-E.

In order to output the signals for pre-heater operation and supply fan 

monitor output with delay operation (for after heater), a setting change 

from PZ-62DR-E is necessary.

■  Connection Diagram

Note

● 

Be careful that the external device cable that connects to the PZ-

4GS-E do not touch the surface of the Lossnay unit control board.  
It could lead to erroneous operation.

● 

Tighten the terminal block screws with a torque of 0.5N

m or less 

to avoid damaging the circuit board.

● 

When connecting two cables to one location on the terminal block, 
use a crimped terminal to ensure they are connected. Do not 
connect three or more cables.

● 

Especially when using Pre-heater output signal or After-heater 
output signal,refer to Lossnay installation and instruction manual.

Indicator, 

external 

device, etc.

Indicator, 

external 

device, etc.

Power Supply

Max. 240VAC,  1A

 

24VDC,   1A

(1.5A for COM terminal)

Min.  208VAC,  100mA

 

5VDC,   100mA

Indicator, 

external 

device, etc.

Indicator, 

external 

device, etc.

Crimped Terminal Connection Example

6 mm (15/64 inches) or less

If there is no insulating coating, 

be sure to perform insulation 
treatment.

Crimped terminal

Terminal block

Содержание Lossnay PZ-4GS-E

Страница 1: ...re flammable gases may leak If gas should leak or accumulate around the product fire or explosion could result Do not use the product in special environments The product could be damaged if it is used in locations subject to large quantities of oil including machine oil steam or sulfide gas Do not install the unit in a place where the temperature rises above 40 C 104 F where large amounts of oil s...

Страница 2: ...Connecting the Cable Connect the connector CN500 on the PZ 4GS E to the connector CN50 on the Lossnay unit control board using the included connection cable Note Insert the cable all the way until a locking sound is heard Be sure not to apply force to the connector 3 4 Wiring the External Device 1 Remove the bush on the Lossnay unit and install a cable gland with two holes 2 Pass the external devi...

Страница 3: ...ries The setting may differ according to the type of Lossnay series Be sure to refer each Lossnay unit installation manual for detail setting The output signals from each terminal can be changed arbitrarily from PZ 62DR E In order to output the signals for pre heater operation and supply fan monitor output with delay operation for after heater a setting change from PZ 62DR E is necessary Connectio...

Страница 4: ...on cables securely connected to the terminal block Are the connection cables arranged so that they are not touching the surface of the Lossnay unit control board Are any connectors on the circuit board disconnected Are the function settings set correctly 7 Trial Operation Conduct a trial operation following the installation and instruction manual for the Lossnay unit 5 Function Settings When PZ 62...

Отзывы: