U-88
CHAPTER 10
•
Ventilation Standards in Each Country
Occupancy
Category
People Outdoor
Air Rate
R
p
Area Outdoor
Air Rate
R
a
Notes
Default Values
Air
Class
Occupant
Density
(see Note 4)
Combined Outdoor Air
Rate (see Note 5)
cfm/person L/s·person
cfm/ft
2
L/s∙m
2
#/1000 ft
2
or #/100 m
2
cfm/person
L/s·person
Miscellaneous Spaces
Bank vaults/safe deposit
5
2.5
0.06
0.3
5
17
8.5
2
Banks or bank lobbies
7.5
3.8
0.06
0.3
15
12
6.0
1
Computer (not printing)
5
2.5
0.06
0.3
4
20
10.0
1
General (excludes manufacturing heavy
industrial and processes using chemicals)
10
5.0
0.18
0.9
7
36
18
3
Pharmacy (prep. area)
5
2.5
0.18
0.9
10
23
11.5
2
Photo studios
5
2.5
0.12
0.6
10
17
8.5
1
Shipping/receiving
10
5
0.12
0.6
B
2
70
35
2
Sorting, packing, light assembly
7.5
3.8
0.12
0.6
7
25
12.5
2
Telephone closets
–
–
0.00
0.0
–
1
Transportation waiting
7.5
3.8
0.06
0.3
100
8
4.1
1
Warehouses
10
5
0.06
0.3
B
–
2
Public Assembly Spaces
Auditorium seating area
5
2.5
0.06
0.3
150
5
2.7
1
Places of religious worship
5
2.5
0.06
0.3
120
6
2.8
1
Courtrooms
5
2.5
0.06
0.3
70
6
2.9
1
Legislative chambers
5
2.5
0.06
0.3
50
6
3.1
1
Libraries
5
2.5
0.12
0.6
10
17
8.5
1
Lobbies/prefunction
5
2.5
0.06
0.3
150
5
2.7
1
Museums (children's)
7.5
3.8
0.12
0.6
40
11
5.3
1
Museums/galleries
7.5
3.8
0.06
0.3
40
9
4.6
1
Residential
Dwelling unit
5
2.5
0.06
0.3
F,G
F
1
Common corridor
–
–
0.06
0.3
1
Retail
Sales (except as below)
7.5
3.8
0.12
0.6
15
16
7.8
2
Mall common areas
7.5
3.8
0.06
0.3
40
9
4.6
1
Barbershop
7.5
3.8
0.06
0.3
25
10
5.0
2
Beauty and nail salons
20
10
0.12
0.6
25
25
12.4
2
Pet shops (animal areas)
7.5
3.8
0.18
0.9
10
26
12.8
2
Supermarket
7.5
3.8
0.06
0.3
8
15
7.6
1
Coin-operated laundries
7.5
3.8
0.12
0.6
20
14
7.0
2
Sports and Entertainment
Sports arena (play area)
–
–
0.30
1.5
E
–
1
Gym, stadium (play area)
–
–
0.30
1.5
30
2
Spectator areas
7.5
3.8
0.06
0.3
150
8
4.0
1
Swimming (pool & deck)
–
–
0.48
2.4
C
–
2
Disco/dance floors
20
10
0.06
0.3
100
21
10.3
2
Health club/aerobics room
20
10
0.06
0.3
40
22
10.8
2
Health club/weight rooms
20
10
0.06
0.3
10
26
13.0
2
Bowling alley (seating)
10
5
0.12
0.6
40
13
6.5
1
Gambling casinos
7.5
3.8
0.18
0.9
120
9
4.6
1
Game arcades
7.5
3.8
0.18
0.9
20
17
8.3
1
Stages, studios
10
5
0.06
0.3
D
70
11
5.4
1
GENERAL NOTES FOR TABLE 6-1
1 Related requirements: The rates in this table are based on all other applicable requirements of this standard being met.
2 Environmental Tobacco Smoke: This table applies to ETS-free areas. Refer to Section 5.17 for requirements for buildings containing ETS areas and ETS-free areas.
3 Air density: Volumetric airfl ow rates are based on an air density of 0.075 lbda/ft3 (1.2 kgda/m3), which corresponds to dry air at a barometric pressure of 1 atm
(101.3 kPa) and an air temperature of 70°F (21°C). Rates may be adjusted for actual density but such adjustment is not required for compliance with this standard.
4 Default occupant density: The default occupant density shall be used when actual occupant density is not known.
5 Default combined outdoor air rate (per person): This rate is based on the default occupant density.
6 Unlisted occupancies: If the occupancy category for a proposed space or zone is not listed, the requirements for the listed occupancy category that is most similar in terms
of occupant density, activities, and building construction shall be used.
ITEM-SPECIFIC NOTES FOR TABLE 6-1
A For high school and college libraries, use values shown for Public Assembly Spaces - Libraries.
B Rate may not be suffi cient when stored materials include those having potentially harmful emissions.
C Rate does not allow for humidity control. Additional ventilation or dehumidifi cation may be required to remove moisture. “Deck area” refers to the area surrounding the pool
that would be expected to be wetted during normal pool use, i.e., when the pool is occupied. Deck area that is not expected to be wetted shall be designated as a space type
(for example, “spectator area”).
D Rate does not include special exhaust for stage effects, e.g., dry ice vapors, smoke.
E When combustion equipment is intended to be used on the playing surface, additional dilution ventilation and/or source control shall be provided.
F Default occupancy for dwelling units shall be two persons for studio and one-bedroom units, with one additional person for each additional bedroom.
G Air from one residential dwelling shall not be recirculated or transferred to any other space outside of that dwelling.
Содержание Lossnay LGH-F1200RX5-E
Страница 2: ...Y11 001 Jun 2012 MEE ...
Страница 7: ......
Страница 8: ...Lossnay Unit ...
Страница 9: ......
Страница 10: ...CHAPTER 1 Ventilation for Healthy Living ...
Страница 23: ......
Страница 24: ...CHAPTER 2 Lossnay Construction and Technology ...
Страница 30: ...CHAPTER 3 General Technical Considerations ...
Страница 45: ......
Страница 46: ...U 37 CHAPTER 4 Characteristics CHAPTER 4 Characteristics ...
Страница 59: ......
Страница 60: ...CHAPTER 5 System Design Recommendations ...
Страница 67: ......
Страница 68: ...CHAPTER 6 Examples of Lossnay Applications ...
Страница 79: ......
Страница 80: ...CHAPTER 7 Installation Considerations ...
Страница 83: ......
Страница 84: ...CHAPTER 8 Filters ...
Страница 90: ...CHAPTER 9 Service Life and Maintenance ...
Страница 93: ......
Страница 94: ...CHAPTER 10 Ventilation Standards in Each Country ...
Страница 99: ......
Страница 100: ...CHAPTER 11 Lossnay Q and A ...