U-8
CHAPTER 1
•
Ventilation for Healthy Living
4.3 Measuring the Air Volume and Static Pressure
Mitsubishi Electric measures the Lossnay’s air volume and static pressure with a device as shown below according to Japan
Industrial Standards (JIS B 8628).
Measuring Device Using Orifice (JIS B 8628 Standards)
St
atic pr
essur
e (
H
)
Air volume (Q)
Measurement Method
The unit is operated with the throttle device fully closed. There is no air flow at this time, and the air volume is 0. The maximum
point of the static pressure (Point A, the static pressure at this point is called the totally closed pressure) can be obtained. Next,
the throttle device is gradually opened, the auxiliary fan is operated, and the median points (Points B, C and D) are obtained.
Finally, the throttle device is completely opened, and the auxiliary fan is operated until the static pressure in the chamber reaches 0.
The maximum point of the air volume (Point E, the air volume at this point is called the fully opened air volume) is obtained. The
points are connected as shown below, and are expressed as air volume, static pressure curves (Q-H curve).
C
onnection
W
ind disper
sing place
C
onnection
Smoothing
grid
Smoothing
grid
Supply
Air
(SA)
Chamber
Return
Air
(RA)
Smoothing
net
Smoothing
net
Wind gauge
duct path
Orifice
Wind gauge
duct path
Orifice
Damper
Blower
Blower
Test unit
Test unit
Static pressure in chamber
(Static pressure measurement)
Static pressure in chamber
(Static pressure measurement)
Pressure
difference before
and after orifice
(Air volume
measurement)
A) When measuring the supply air volume (with the orifice plate)
B) When measuring the return air volume (with the orifice plate)
Содержание Lossnay LGH-F1200RX5-E
Страница 2: ...Y11 001 Jun 2012 MEE ...
Страница 7: ......
Страница 8: ...Lossnay Unit ...
Страница 9: ......
Страница 10: ...CHAPTER 1 Ventilation for Healthy Living ...
Страница 23: ......
Страница 24: ...CHAPTER 2 Lossnay Construction and Technology ...
Страница 30: ...CHAPTER 3 General Technical Considerations ...
Страница 45: ......
Страница 46: ...U 37 CHAPTER 4 Characteristics CHAPTER 4 Characteristics ...
Страница 59: ......
Страница 60: ...CHAPTER 5 System Design Recommendations ...
Страница 67: ......
Страница 68: ...CHAPTER 6 Examples of Lossnay Applications ...
Страница 79: ......
Страница 80: ...CHAPTER 7 Installation Considerations ...
Страница 83: ......
Страница 84: ...CHAPTER 8 Filters ...
Страница 90: ...CHAPTER 9 Service Life and Maintenance ...
Страница 93: ......
Страница 94: ...CHAPTER 10 Ventilation Standards in Each Country ...
Страница 99: ......
Страница 100: ...CHAPTER 11 Lossnay Q and A ...