11

English

Mode

No pulse input (factory setting)

Pulse input

OFF

ON

2

2

SW2

This sets the fan to run forcibly for 30 minutes when operation starts
to ventilate the indoor area. After 30 minutes, the system switches
to enable fan speed adjustment from the remote controller. Use this
setting if the indoor air is contaminated at night when the system is
shut down and you desire to ventilate the indoor area quickly when
operation is started in the morning.

Set as shown when connecting the pulse signal equipment from a
building maintenance system to an external input.

Mode

Operation

OFF

ON

SW2

Operation

Normal (factory setting)

Runs the fan forcibly for 30 minutes when operation
starts.

OFF

ON

3

3

SW2

The fan speed alternates between the
High (Extra high) and Low instead of
the remote controller setting.

Power Ventilation
Normal (factory setting)

4
5

Power Supply

Power Exhaust

Power Save
Ventilation

Runs the exhaust fan (EA) at Low
speed constantly.
Alternates the supply fan (SA) speed
between the High (Extra high) and
Low.

Runs the supply fan (SA) at Low
speed constantly.
Alternates the exhaust fan (EA)
speed between the High (Extra high)
and Low.

Runs the supply fan (SA) and exhaust
fan (EA) at Low speed constantly.
Switches to the Power Save
Ventilation setting regardless of the
remote controller’s High or Low.

4
5

4
5

4
5

Settings for pulse input

1

Switching to power supply/exhaust when operation starts

2

This sets the ventilation system to in the case that ventilation balance
in accordance with the use environment and installation location is
selected. There are four possible setting modes.

Switching to the multi ventilation mode

3

*

When using the Remote Controller (PZ-60DR-E), operation of the
Extra Low fan speed button initiates the Extra Low fan speed
operation both at the supply (SA) and exhaust (EA) sides.
Independent operation of the supply (SA) or exhaust (EA) side is
prohibited when it is set at the Extra Low fan speed.

Controls stop and start operation by turning the power supply (220-
240 V) for the Lossnay on and off.

Power supply ON/OFF function (cannot be set when
PZ-41SLB-E is used)

4

Mode

Off

(factory setting)

On

OFF

ON

6

6

SW2

Operation

Stop and start is performed according to
SW5-4 settings when the power is on.

Operation possible by turning power on
and off.

Two thermistors in the Lossnay unit detect the indoor (RA) and
outdoor (OA) air temperatures and automatically select the
“Lossnay ventilation” or “Bypass ventilation”. With this mode,
however, priority is given to the “Bypass ventilation”.
* This setting reflects to the night purge operation condition.

Bypass automatic ventilation priority setting

5

OFF

ON

7

7

SW2

Operation

When outdoor temperature (OA) is 28˚C or higher within
24 hours, then Bypass ventilation starts by the
comparison OA and RA temperature. The lowest RA
temperature of Bypass operation is 24˚C (factory setting)
When the night purge is set by the remote controller PZ-
60DR-E, night purge operation starts at a temperature
of 28˚C (within 24 hours).

When outdoor temperature (OA) is 17˚C or higher within
24 hours, then Bypass ventilation starts by the
comparison OA and RA temperature. The lowest RA
temperature of Bypass operation is 19˚C
When the night purge is set by the remote controller PZ-
60DR-E, night purge operation starts at a temperature
of 17˚C (within 24 hours).

Setting for TM4 

90

 output

6

Operation

Operation monitor output
Corresponds to operation mode output (TM4

90

)

based on SW5-2 setting. (factory setting)

Operation monitor output with delay function 1
Corresponds to operation mode output (TM4

90

)

supply fan with following function.

 • Starts the output (TM4

90

) 10 seconds after supply

fan operates.

 • Lossnay continues to operate for 3minutes after

stopping the output (TM4

90

)

Caution : Fan may be operating after turn off the

switch of the remote controller.

OFF

ON

8

8

SW2

Extra High/High switch setting

7

Operation

Supply fan (SA) - High fixed (factory setting)

Supply fan (SA)  - Extra High fixed

Exhaust fan (EA) - High fixed (factory setting)

Exhaust fan (EA) - Extra High fixed

OFF

ON

9

9

10

10

SW2

Select this function when increased air volume is required or when
the duct piping is longer.

Function settings (continued)

Set for delay operation at heating or cooling start-up

8

Delays Lossnay operation for 30 minutes when City Multi or Mr.
Slim starts operating or when a external device starts operating. (If
the PZ-41SLB-E is used, set it at the remote control. )

Mode

No operation delay (factory setting)

Operation delay of 30 minutes
* This function is invalid with in 2 hours’ restart

OFF

ON

1

1

SW5

Operation output monitor

9

Mode

Corresponds to operation mode output (TM4 

90

)

exhaust fan (factory setting)

Corresponds to operation mode output (TM4 

90

)

supply fan
(The operation monitor output is off when the supply
fan is stopped for operation in cold regions or during
the City Multi or Mr. Slim defrost mode.)

OFF

ON

2

2

SW5

This setting is available when SW2-8 is OFF.

Содержание Lossnay LGH-150RX5-E

Страница 1: ...s a result of incomplete combustion Do not use at a place where it is exposed to high temperatures 40 C or higher naked flames or in environment with combustible fumes It could cause fire Do not use in an environment such as a chemical factory where hazardous gases such as acidic gases alkaline gases organic solvent fumes paint fumes or gases containing corrosive components are generated It could ...

Страница 2: ...200 RX5 Model A B C D Weight kg LGH 150 RX5 1004 690 690 1045 105 LGH 200 RX5 1231 917 917 1272 118 Unit mm Accessory parts Duct connecting flanges x4 Mounting screws x16 Slim Lossnay connection cable gray two wires x1 Ceiling suspension fixture 4 15 x 30 oval SA supply air RA return air EA exhaust air outlet OA outside air intake Core air filter High Efficiency filter fan maintenance space Lossna...

Страница 3: ...de air intake Supply air grille not included Except the 150 and 200 RX5 Remote controller optional parts EA exhaust air outlet OA outside air intake It can be installed by inverting the top and the bottom After installing the duct connecting flange remove the maintenance cover Turn the cover by 180 and then reinstall it Maintenance space Lossnay unit Inspection opening EA exhaust air outlet OA out...

Страница 4: ...is recommended that the indoor ductwork be covered with insulation material Do not carry out the following types of duct construction Doing so could cause a drop in the air volume and generate abnormal noises 5 When changing the direction of the out door side duct EA OA Except for LGH 150 and 200 RX5 1 Removal of flange cover Unscrewing the flange cover mounting screws 4 pcs remove the flange cove...

Страница 5: ...is product the wiring installation method will vary according to the design of the system Perform electrical installation to meet local electrical regulations Always use double insulated PVC cable for the transmission cables Wiring work must be performed by qualified professionals All supply circuits must be disconnected before obtaining access to the terminal devices M1 Motor for exhaust fan M2 M...

Страница 6: ...onnector of control board 2 1 TM4 S B A TB5 M NET When the optional Remote Controller PZ 60DR E is used as the M NET System connect it to 1 2 of TM4 terminal block and connect M NET transmission wire to A B on TB5 terminal block 2nd remote controller Max 2 remote controllers installable 2 PZ 41SLB E and PZ 52SF E cannot be used when using PZ 60DR E M NET Transmission cable Shielded wire 2nd or lat...

Страница 7: ...nnected to single input terminal is up to 4 wires for ø0 65 PVC wire or 0 3 mm2 stranded wire It is up to 2 wires for any other wires PZ 41SLB E cannot be used when MELANS centralized control of the Lossnay is used PZ 60DR E and PZ 41SLB E cannot be installed simultaneously 1 Connect the output signal cable from the external device to the input terminal block TM2 of the external controller CAUTION...

Страница 8: ...3 3 and the negative side to 1 1 1 1 1 2 Confirm that the pulse input switch SW2 2 is set to OFF Set to OFF at time of shipment When the external device has a charged operating signal of 12 VDC or 24 VDC Connect the operating signal wire from the external device via the remote output to 1 and 2 on the external control input terminal block TM2 No polarity 1 Move the pulse input switch SW2 2 to the ...

Страница 9: ...y Contactor rating DC 1 mA When connecting to the City Multi Lossnay remote controller PZ 52SF E or Mitsubishi Electric Air Conditioner Network System MELANS 10 Remote ON OFF adaptor Optional PAC SA88HA E When SW1 is ON fan speed of the Lossnay will be set to Low regardless of the remote control setting Use this in such a way that it ventilates at High fan speed normally and when the external sens...

Страница 10: ...roller When interlocking with Mitsubishi Free Plan air conditioner Incase of PZ 60DR E Limit the total length of transmission wires no longer than 500 m Limit the wiring length between Lossnay and the power supply unit Optional or the outdoor unit no longer than 200 m M NET transmission cable Lossnay M NET transmission cable Power supply unit Lossnay MELANS M NET transmission cable Air conditioner...

Страница 11: ...door OA air temperatures and automatically select the Lossnay ventilation or Bypass ventilation With this mode however priority is given to the Bypass ventilation This setting reflects to the night purge operation condition Bypass automatic ventilation priority setting 5 OFF ON 7 7 SW2 Operation When outdoor temperature OA is 28 C or higher within 24 hours then Bypass ventilation starts by the com...

Страница 12: ...pply fan is stopped during defrosting of the air conditioner when Mr Slim or City Multi indoor unit is connected to a duct When the outdoor air is lower than 15 C stop the operation of exhaust fan OA stop operation at cold region Operation Exhaust fan operation factory setting Exhaust fan stop exhaust fan operation at Low speed at outdoor air lower than 15 C OFF ON 3 3 SW5 Settings for automatic r...

Страница 13: ...the external device has come off of the external control input terminal Check in the case of multiple units whether the Main Sub selection switch on the Lossnay unit which is connected to the external control input terminal is set on the Master setting and check whether the Main Sub selection switch on other Lossnay units are set to Sub Check that the trial operation switch SW2 1 is set to off Cha...

Отзывы: