5 MODBUS/TCP (SLAVE)
5.2 Communication Setting
77
5
Precautions
■
About transmission delay
"Transmission delay" is a setting for low-speed devices that cannot respond quickly to transmission responses.
"Transmission delay" is initially set to 0 ms and it is necessary to set it with GT Designer3 (GOT2000) in order to change it.
For details on settings, refer to the following..
GOT2000 Series Connection Manual (Microcomputers, MODBUS/Fieldbus Products, Peripherals)
■
Error code (MODBUS Exception Codes) returned by LE7-40GU (slave) to the MODBUS master
equipment
LE7-40GU (slave) supports the following error codes (MODBUS Exception Codes) in response to a request from the
MODBUS master equipment.
When the following errors occur, LE7-40GU will not generate a system alarm.
This section explains the contents, cause, and remedy for each error code.
• Commonly generated error codes for requests from master equipment
• Error code generated in response to a read request from the master equipment
• Error code generated in response to a write request from the master equipment
H184(388)
Reel diameter input
Setting
0
2000
mm
H185(389)
H186(390)
H187(391)
H188(392)
H189(393)
H18A(394)
H18B(395)
H18C(396)
H18D(397)
H18E(398)
H18F(399)
Error code (HEX)
Category
Contents
Cause
Remedy
0x01
ILLEGAL FUNCTION (illegal
function code)
A function code not supported
by LE7-40GU was received.
A function code not supported by LE7-40GU was
received.
Error code (HEX)
Category
Contents
Cause
Remedy
0x02
Read/Write
ILLEGAL DATAADDRESS
(illegal data address)
You have accessed a device
out of range.
Please check whether the device to be accessed is
incorrect.
Error code (HEX)
Category
Contents
Cause
Remedy
0x02
Read/Write
ILLEGAL DATAADDRESS
(illegal data address)
You have accessed a device
out of range.
Please check whether the device to be accessed is
incorrect.
0x03
Write
ILLEGAL DATA VALUE (illegal
data value)
The consistency of the request
packet (the number of writing
points, the number of bytes of
write data and the number of
write data) is not established.
Make sure that normal packets are being transmitted
from the master equipment.
Request
code
Name
Monitor/
settings
Extension
option
Minimum value
Maximum value
Unit
Содержание LE7-40GU
Страница 1: ...LE7 40GU INSTRUCTION MANUAL Communication ...
Страница 2: ......
Страница 10: ...8 TRADEMARKS 150 ...
Страница 11: ...9 CONTENTS ...
Страница 37: ...3 CC LINK IE FIELD NETWORK BASIC COMMUNICATION 3 3 Reference Program 35 3 ...
Страница 38: ...36 3 CC LINK IE FIELD NETWORK BASIC COMMUNICATION 3 3 Reference Program ...
Страница 39: ...3 CC LINK IE FIELD NETWORK BASIC COMMUNICATION 3 3 Reference Program 37 3 ...
Страница 40: ...38 3 CC LINK IE FIELD NETWORK BASIC COMMUNICATION 3 3 Reference Program ...
Страница 57: ...4 SLMP COMMUNICATION 4 3 Reference Program 55 4 Program example ...
Страница 58: ...56 4 SLMP COMMUNICATION 4 3 Reference Program ...
Страница 59: ...4 SLMP COMMUNICATION 4 3 Reference Program 57 4 ...
Страница 60: ...58 4 SLMP COMMUNICATION 4 3 Reference Program ...
Страница 61: ...4 SLMP COMMUNICATION 4 3 Reference Program 59 4 ...
Страница 82: ...80 5 MODBUS TCP SLAVE 5 3 Reference Program Program example ...
Страница 83: ...5 MODBUS TCP SLAVE 5 3 Reference Program 81 5 ...
Страница 84: ...82 5 MODBUS TCP SLAVE 5 3 Reference Program ...
Страница 85: ...5 MODBUS TCP SLAVE 5 3 Reference Program 83 5 ...
Страница 86: ...84 5 MODBUS TCP SLAVE 5 3 Reference Program ...
Страница 110: ...108 6 N N NETWORK 6 4 Reference Program Program example ...
Страница 111: ...6 N N NETWORK 6 4 Reference Program 109 6 ...
Страница 112: ...110 6 N N NETWORK 6 4 Reference Program ...
Страница 147: ...7 MODBUS RTU ASCII SLAVE 7 4 Reference Program 145 7 Function code H03 Read holding register ...
Страница 149: ...7 MODBUS RTU ASCII SLAVE 7 4 Reference Program 147 7 ...
Страница 153: ......