
13
Installation
4
en
< Figure 4.1.8 >
Unit
Control and
electrical
box
Unit
Control and electrical box
Fix the unit using the 2 screws.
* If it is difficult to access with power
tool, use hand tool instead.
3. Referring to "How to access Internal Components and Control and Electrical Box", fix the unit to the back plate using the included 2 screws (accessory items).
CAUTION: BEFORE performing field piping, be sure to fit and tighten these two screws.
Otherwise, the hook could be disengaged, and the unit could fall down.
<Accessory>
Screw M5×8
<Figure 4.1.10>
<Figure 4.1.11>
<Figure 4.1.12>
Unit
Control and
electrical box
Fix the unit using the 2 screws.
4.2 Water Quality and System Preparation
General
• The water in both primary and sanitary circuit should be clean and with pH value of 6.5-8.0.
• The followings are the maximum values;
Calcium: 100mg/L, Ca hardness: 250mg/L
Chlorine: 100mg/L, Copper: 0.3mg/L
• Other constituents should be to European Directive 98/83 EC standards.l
• In known hard water areas, to prevent/minimise scaling, it is beneficial to restrict
the routine stored water temperature (DHW max. temp.) to 55°C.
Anti-Freeze
Anti-freeze solutions should use propylene glycol with a toxicity rating of Class 1
as listed in Clinical Toxicology of Commercial Products, 5th Edition.
Note:
1. Ethylene glycol is toxic and should NOT be used in the primary water
circuit in case of any cross-contamination of the potable circuit.
2. For 2-zone valve ON/OFF control, propylene glycol should be used.
New Installation (primary water circuit)
• Before connecting outdoor unit, thoroughly cleanse pipework of building debris,
solder etc using a suitable chemical cleansing agent.
• Flush the system to remove chemical cleanser.
• For all packaged model systems, and the split model or PUMY system without
booster heater, add a combined inhibitor and anti-freeze solution to prevent
damage to the pipework and system components.
• For split model systems the responsible installer should decide if anti-freeze
solution is necessary for each site’s conditions. Corrosion inhibitor however
should ALWAYS be used.
Note:
For 2-zone temperature control system, the value in the table above
excludes the amount of stored water in zone2.
Minimum amount of water required in the space
heating/cooling circuit
Outdoor heat pump unit
Minimum water quantity [L]
Packaged model PUHZ-WM85
PUHZ-WM112
Split model
SUZ-SWM40
SUZ-SWM60
SUZ-SWM80
PUHZ-SW50
PUHZ-FRP71
PUHZ-SW75
PUHZ-SW100
PUHZ-SW120
PUHZ-SHW80
PUHZ-SHW112
PUHZ-SHW140
PUMY-P112
PUMY-P125
PUMY-P140
<Table 4.2.1>
Existing Installation (primary water circuit)
• Before connecting outdoor unit the existing heating circuit MUST be chemically
cleansed to remove existing debris from the heating circuit.
• Flush the system to remove chemical cleanser.
• For all packaged model systems add a combined inhibitor and anti-freeze
solution to prevent damage to the pipework and system components.
• For split model systems the responsible installer should decide if anti-freeze
solution is necessary for each site’s conditions. Corrosion inhibitor however
should ALWAYS be used.
When using chemical cleansers and inhibitors always follow manufacturer’s
instructions and ensure the product is appropriate for the materials used in
the water circuit