70
5 WIRING
5.5 External Input Connection Connector [FX5-SSC-S]
Wiring example for manual pulse generator/incremental synchronous encoder
Wire the manual pulse generator/incremental synchronous encoder of differential output type and voltage output type/open-
collector type as follows.
Switch the input type of FX5-SSC-S by "[Pr.89] Manual pulse generator/Incremental synchronous encoder input type
selection".
Use the external 5 V power supply (5 V DC±5%) for the power supply of the manual pulse generator/incremental synchronous
encoder.
Connect the 0 V (-) of the manual pulse generator/incremental synchronous encoder and the SG of FX5-SSC-S.
Select the external power supply with due consideration for the capacity of manual pulse generator/incremental synchronous
encoder.
■
Manual pulse generator/Incremental synchronous encoder of differential output type
■
Manual pulse generator/Incremental synchronous encoder of voltage output type/open-
collector type
FX5-SSC-S
HAH
(A+)
HAL
(A-)
HBH
(B+)
HBL
(B-)
HAH
(A+)
HAL
(A-)
HBH
(B+)
HBL
(B-)
External 5 V
power supply
5 V
0 V
Recommended wiring example
FG
FG
Twisted pair
Shield
Manual pulse generator/
Incremental synchronous encoder
SG
External 5 V
power supply
FG
FG
HA
(A)
HB
(B)
SG
HA
(A)
HB
(B)
5 V
0 V
FX5-SSC-S
Recommended wiring example
Manual pulse generator/
Incremental synchronous encoder
Shield
Twisted pair
Downloaded from
Содержание FX5-40SSC-G
Страница 2: ...Downloaded from ManualsNet com search engine ...
Страница 103: ...APPX Appendix 8 Operation Examples 101 A Downloaded from ManualsNet com search engine ...
Страница 104: ...102 APPX Appendix 8 Operation Examples Positioning start program Downloaded from ManualsNet com search engine ...
Страница 121: ...Downloaded from ManualsNet com search engine ...