FX2N-8AD Analog input block
Specifications 7
7-2
Table 7.2: Power supply specifications
Item
Specifications
Interface driving
power supply
24 V DC±10%, 80 mA (maximum), supplied via terminal from outside
CPU driving power
supply
5 V DC, 50 mA, supplied via extension cable from PLC main unit
Table 7.3: Performance specifications
Item
Specifications
Conversion speed
• When only voltage input and current input are used
500
µ
s x Number of used channels
• When thermocouple input is used for 1 or more channels
Channel for voltage/current input: 1 ms x Number of used channels
Channel for thermocouple input: 40 ms x Number of used channels
(Number of used channels indicates number of all channels used for voltage
input, current input or thermocouple input.)
Insulation method
Photocoupler insulates analog input area from PLC.
DC/DC converter insulates power supply from analog I/O.
Channels are not insulated each other.
Number of occupied
I/O points
8 points (including input points and output points)
Applicable PLC
FX
0N
/FX
1N
/FX
2N
/FX
2NC
/FX
3U
/FX
3UC
Series PLC
(For connection to FX
2NC
Series PLC, FX
2NC
-CNV-IF is required.)
(For connection to FX
3UC
Series PLC, FX
3UC
-1PS-5V or FX
2NC
-CNV-IF is required.)
Built-in memory
EEPROM
Содержание FX2N-8AD
Страница 4: ...FX2N 8AD Analog input block ii ...
Страница 8: ...FX2N 8AD Analog input block vi ...
Страница 14: ...FX2N 8AD Analog input block External Dimensions 2 2 2 MEMO ...
Страница 16: ...FX2N 8AD Analog input block Part Name 3 3 2 MEMO ...
Страница 20: ...FX2N 8AD Analog input block Connection to PLC 5 5 2 MEMO ...
Страница 24: ...FX2N 8AD Analog input block Wiring 6 6 4 MEMO ...
Страница 70: ...FX2N 8AD Analog input block Buffer Memory BFM 8 8 42 MEMO ...
Страница 84: ...FX2N 8AD Analog input block Example program 10 10 6 MEMO ...
Страница 87: ......