R a c k m o u n t i n g t h e F T 5 0 0 0
FT5000 HANDBOOK A/9
Install the server in the rack
Read the advisory information at the front of this chapter
.
W
WA
AR
RN
NIIN
NG
G
The FT5000 server is heavy. It is not advisable to lift it without adequate lifting equipment. The
minimum server configuration weighs 38 kg; the maximum weighs 45 kg.
1.
Pull the telescoping centre bars out of the large outer bars until they are fully extended and
locked in place.
2.
Use a mechanical assist unit to carefully pick up the server; gently slide the small bars attached
to each side of the server into the extended centre bars.
1
3
2
4
2
1
Small outer bar
2
Centre bar
3
Large outer bar
4
Safety latch
3.
When the server stops, press in on the safety latches on the small bars and gently slide the
server into the rack.
4.
Connect all external cables and the power cord(s) to the server.