(2) Low Voltage Directive
We have self-confirmed our inverters as products compliant to the Low Voltage Directive (Conforming standard EN 50178) and affix the CE
mark on the inverters.
Outline of instructions
* Do not use an earth leakage current breaker as an electric shock protector without connecting the equipment to the earth. Connect the
equipment to the earth securely.
* Wire the earth terminal independently. (Do not connect two or more cables to one terminal.)
* Use the cable sizes on
page
8 under the following conditions.
⋅
Surrounding air temperature: 40°C (104°F) maximum
If conditions are different from above, select appropriate wire according to EN60204 Appendix C TABLE 5.
* Use a tinned (plating should not include zinc) crimping terminal to connect the ground cable. When tightening the screw, be careful not
to damage the threads.
For use as a product compliant with the Low Voltage Directive, use PVC cable whose size is indicated on
* Use the moulded case circuit breaker and magnetic contactor which conform to the EN or IEC Standard.
* When using an earth leakage current breaker, use a residual current operated protective device (RCD) of type B (breaker which can
detect both AC and DC). If not, provide double or reinforced insulation between the inverter and other equipment, or put a transformer
between the main power supply and inverter.
* Use the inverter under the conditions of overvoltage category II (usable regardless of the ground condition of the power supply),
overvoltage category III (usable with the earthed-neutral system power supply, 400V class only) and pollution degree 2 or lower
specified in IEC664.
⋅
To use the inverter of 00770 or more (IP00) under the conditions of pollution degree 2, install it in the enclosure of IP 2X or higher.
⋅
To use the inverter under the conditions of pollution degree 3, install it in the enclosure of IP54 or higher.
⋅
To use the inverter of 00620 or less (IP20) outside of an enclosure in the environment of pollution degree 2, fix a fan cover with fan
cover fixing screws enclosed.
* On the input and output of the inverter, use cables of the type and size set forth in EN60204 Appendix C.
* The operating capacity of the relay outputs (terminal symbols A1, B1, C1, A2, B2, C2) should be 30VDC, 0.3A. (Relay output has basic
isolation from the inverter internal circuit.)
* Control circuit terminals on
page
4 are safely isolated from the main circuit.
* Environment
Details are given in the technical information "Low Voltage Directive Conformance Guide" (BCN-A21041-203). Please contact your sales
representative.
FR-F720-00105 to 00250
FR-F740-00083, 00126
FR-F720-00340 to 00630
FR-F740-00170 to 00380
FR-F720-00770 to 01250
FR-F740-00470, 00620
During Operation
In Storage
During Transportation
Surrounding air
temperature
LD: -10°C to +50°C (14°F to 122°F)
SLD (initial setting): -10°C to +40°C (14°F
to 104°F)
-20°C to +65°C
(-4°F to +149°F)
-20°C to +65°C
(-4°F to +149°F)
Ambient humidity
90% RH or less
90% RH or less
90% RH or less
Maximum altitude
1000m (3280.80feet)
1000m (3280.80feet)
10000m (32808feet)
Fan cover
fixing screw
Fan cover
Fan
Fan cover
fixing screws
Fan cover
Fan
Fan cover
fixing screw
Fan cover
Fan