16
PARAMETER
260
PWM frequency
automatic
switchover
0, 1
1
261
Power failure stop
selection
0, 1, 2
0
262
Subtracted
frequency at
deceleration start
0 to 20Hz
3Hz
263
Subtraction starting
frequency
0 to 120Hz,
9999
50Hz
264
Power-failure
deceleration time 1
0 to 3600/ 360s
5s
265
Power-failure
deceleration time 2
0 to 3600/ 360s,
9999
9999
266
Power failure
deceleration time
switchover
frequency
0 to 400Hz
50Hz
267
Terminal 4 input
selection
0, 1, 2
0
268
Monitor decimal
digits selection
0, 1, 9999
9999
269
Parameter for manufacturer setting.
Do not make setting.
299
Rotation direction
detection selection
at restarting
0, 1, 9999
9999
331
RS-485
communication
station
0 to 31
(0 to 247)
0
332
RS-485
communication
speed
3, 6, 12, 24,
48, 96, 192, 384
96
333
RS-485
communication stop
bit length
0, 1, 10, 11
1
334
RS-485
communication
parity check
selection
0, 1, 2
2
335
RS-485
communication
number of retries
0 to 10, 9999
1
336
RS-485
communication
check time interval
0 to 999.8s,
9999
0s
337
RS-485
communication
waiting time setting
0 to 150ms,
9999
9999
338
Communication
operation command
source
0, 1
0
339
Communication
speed command
source
0, 1, 2
0
340
Communication
startup mode
selection
0, 1, 2, 10, 12
0
341
RS-485
communication
CR/LF selection
0, 1, 2
1
342
Communication
EEPROM write
selection
0, 1
0
Parameters
Name
Setting Range
Initial Value
343
Communication error
count
⎯
0
495
Remote output
selection
0, 1
0
496
Remote output data 1
0 to 4095
0
497
Remote output data 2
0 to 4095
0
503
Maintenance timer
0 (1 to 9998)
0
504
Maintenance timer
alarm output set time
0 to 9998, 9999
9999
549
Protocol selection
0, 1
0
550
NET mode operation
command source
selection
0, 1, 9999
9999
551
PU mode operation
command source
selection
1, 2
2
555
Current average time
0.1 to 1.0s
1s
556
Data output mask
time
0.0 to 20.0s
0s
557
Current average
value monitor signal
output reference
current
0 to 500A/
0 to 3600A *
1
Rated
inverter
current
563
Energization time
carrying-over times
(0 to 65535)
0
564
Operating time
carrying-over times
(0 to 65535)
0
570
Multiple rating
setting
0, 1
0
571
Holding time at a
start
0.0 to 10.0s,
9999
9999
573
4mA Input check
selection
1, 9999
9999
575
Output interruption
detection time
0 to 3600s,
9999
1s
576
Output interruption
detection level
0 to 400Hz
0Hz
577
Output interruption
release level
900 to 1100%
1000%
578
Auxiliary motor
operation selection
0 to 3
0
579
Motor swichover
selection
0 to 3
0
580
MC switching
interlock time
0 to 100s
1s
581
Start waiting time
0 to 100s
1s
582
Auxiliary motor
connection-time
deceleration time
0 to 3600s,
9999
1s
583
Auxiliary motor
disconnection-time
acceleration time
0 to 3600s,
9999
1s
584
Auxiliary motor 1
starting frequency
0 to 400Hz
50Hz
585
Auxiliary motor 2
starting frequency
0 to 400Hz
50Hz
586
Auxiliary motor 3
starting frequency
0 to 400Hz
50Hz
587
Auxiliary motor 1
stopping frequency
0 to 400Hz
0Hz
Parameters
Name
Setting Range
Initial Value
*1
The setting depends on capacities. (01160 or less/01800 or more)