39
2. Basic Operation
2.6 Basic operation procedure (External operation)
1
2
3
4
5
6
7
8
9
10
2.6
Basic operation procedure (External operation)
Select a method to give the frequency command from the list below, and refer to the specified page for its procedure.
2.6.1
Setting the frequency on the operation panel
• Turn ON the STF/STR signal to give a start command.
• Use operation panel (setting dial or UP/DOWN key) to give a frequency command.
• Set
Pr.79
= "3" (External/PU combined operation mode 1).
[Connection diagram]
The following shows the procedure to operate at 30 Hz.
Operating procedure
1.
Changing the operation mode
Set "3" in
Pr.79
. The PU LED and EXT LED turn ON. (To change the setting, refer to
.)
2.
Setting the frequency
Turn the setting dial or press the UP/DOWN key until the target frequency "30.00" (30.00 Hz) appears. The indication
blinks for about 5 seconds.
While the value is blinking, press the SET key to enter the frequency. "F" and "30.00" are displayed alternately. After
about 3 seconds of alternate display, the indication returns to "0.00" (the indication of a monitored value). (If the SET
key is not pressed, the indication of the value returns to "0.00" (0.00 Hz) after about 5 seconds of blinking. In that
case, turn the setting dial or press the UP/DOWN key and set the frequency again.)
3.
Start
→
acceleration
→
constant speed
Turn ON the start switch (STF/STR signal). The frequency value on the monitor increases according to the setting
of
Pr.7 Acceleration time
, and "30.00" (30.00 Hz) appears on the monitor. The RUN LED is ON during forward
rotation and blinks slowly during reverse rotation. (To change the set frequency, return to step 2. The previously set
frequency appears.)
4.
Deceleration
→
stop
Turn OFF the start switch (STF/STR signal). The frequency value on the monitor decreases according to the setting
of
Pr.8 Deceleration time
, "0.00" (0.00 Hz) appears on the monitor, and the motor stops rotating.
Method to give the frequency command
Refer to page
Setting the frequency on the operation panel in the frequency setting mode
Turning ON/OFF switches wired to inverter's terminals (multi-speed setting)
Setting the frequency by inputting voltage signals
Setting the frequency by inputting current signals
Operation panel
Inverter
SD
STF
STR
Forward rotation
start
Reverse rotation
start
Switch
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...