15. (A) Application Parameters
15.4 PID control
• For the terminal used for the SLEEP signal, set "70" (positive logic) or "170" (negative logic) in any parameter from
Pr.190
to Pr.196 (Output terminal function selection)
.
*1
When the PID output shutoff release level is reached during a deceleration stop, output shutoff is released, operation is re-accelerated and PID
control is continued. During deceleration,
Pr.576 Output interruption detection level
is invalid.
Integral stop selection when the frequency is limited (Pr.1015)
• The operation for the integral term can be selected when the frequency or the manipulated amount is limited during PID
control.
• The manipulation range can be selected.
*1
When the frequency reaches the upper limit, or when the PID manipulated amount reaches 100%, the integral stops and the integral term is
retained. When the frequency decreases, the integral does not stop until the manipulated amount reaches -100%, regardless of the output
frequency.
Output frequency
Deviation
When
Pr.554
="0 to 3", reverse operation (
Pr.128
="10")
Pr.576
Pr.577
- 1000%
Cancel
level
RUN
Time
ON
OFF
SLEEP
Less than
Pr.575
Pr.575
or more SLEEP period
PID
Output frequency
Pr.576
RUN
Time
ON
OFF
SLEEP
Deceleration stop
PID
When
Pr.554
="10 to 13", reverse operation (
Pr.128
="10")
Deviation
Pr.577
- 1000%
Cancel
level
Less than
Pr.575
Pr.575
or more
SLEEP period
Pr.1015 setting
Operation at limited frequency
Range of manipulation
0 (initial value)
Integral stop
-100% to +100%
1
2
Integral stop
0% to 100%
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...