246
11. (H) Protective Function Parameters
11.3 Earth (ground) fault detection at start
11.3
Earth (ground) fault detection at start
Select whether to make earth (ground) fault detection at start. When enabled, earth (ground) fault detection is performed
immediately after a start signal input to the inverter.
*1
Gr.1 and Gr.2 are the parameter initial value groups. (Refer to
• If a ground fault is detected at start while
Pr.249
= "1", the output-side earth (ground) fault overcurrent (E.GF) is displayed
and the outputs are shut off.
• When the
Pr.72 PWM frequency selection
setting is high, enable the ground fault detection at start.
NOTE
• Because the detection is performed at start, output is delayed for approx. 20 ms every start.
• Use
Pr.249
to enable/disable ground fault detection at operation start.
Pr.
Name
Initial value
Setting range
Description
Gr.1
Gr.2
249
H101
Earth (ground) fault detection at
start
0
1
0
Earth (ground) fault detection at start
disabled
1
Earth (ground) fault detection at start
enabled
Содержание FR-E800
Страница 17: ...16 1 Introduction 1 3 Related manuals MEMO ...
Страница 51: ...50 2 Basic Operation 2 8 I O terminal function assignment MEMO ...
Страница 89: ...88 3 Parameters 3 4 Parameter list by function group number MEMO ...
Страница 135: ...134 5 Speed Control 5 9 Troubleshooting in the speed control MEMO ...
Страница 153: ...152 6 Torque Control 6 7 Troubleshooting in torque control MEMO ...
Страница 195: ...194 8 E Environment Setting Parameters 8 18 Current average value monitor signal MEMO ...
Страница 237: ...236 10 D Operation Command and Frequency Command 10 6 Operation by multi speed setting MEMO ...
Страница 339: ...338 13 T Multi Function Input Terminal Parameters 13 9 Start signal operation selection MEMO ...
Страница 455: ...454 16 G Control Parameters 16 13 Speed smoothing control MEMO ...
Страница 481: ...480 18 Appendix 18 4 Parameters functions and instruction codes under different control methods MEMO ...