Monitor display and monitor output signal
4.12.4 Terminal FM calibration (calibration parameter C0 (Pr. 900))
(1) FM terminal calibration
(C0 (Pr. 900))
The terminal FM is preset to output pulses. By setting the
FM terminal calibration C0 (Pr. 900)
, the meter connected to the
inverter can be calibrated by parameter setting without use of a calibration resistor.
Using the pulse train output of the terminal FM, a digital display can be provided to connect a digital counter.
The monitor value is 1440 pulses/s output at the full-scale value of monitor description list
(page 154)
(Pr. 54 FM terminal
function selection)
.
∗1
Not needed when the operation panel or parameter unit (FR-PU04/FR-PU07) is used for calibration.
Use a calibration resistor when the indicator (frequency meter) needs to be calibrated by a neighboring device because the indicator is located far from
the inverter. However, the frequency meter needle may not deflect to full-scale if the calibration resistor is connected. In this case, perform calibration
using the operation panel or parameter unit.
∗2
The default settings are 1mA full-scale and 1440 pulses/s terminal FM frequency at 60Hz.
Calibrate the terminal FM in the following procedure.
1) Connect an indicator (frequency meter) across terminals FM-SD of the inverter. (Note the polarity. The terminal FM is
positive)
2) When a calibration resistor has already been connected, adjust the resistance to "0" or remove the resistor.
3) Refer to the monitor description list
(page 154)
and set
Pr. 54
.
When you selected the running frequency or inverter output current as monitor, preset the running frequency or
current value, at which the output signal will be 1440 pulses/s, to
Pr. 55 Frequency monitoring reference
or
Pr. 56 Current
monitoring reference
.
At 1440 pulses/s, the meter generally deflects to full-scale.
By using the operation panel or parameter unit, you can calibrate terminal FM to full scale deflection.
Parameter
Number
Name
Initial Value
Setting Range
Description
C0 (900)
FM terminal calibration
—
—
Calibrates the scale of the meter
connected to terminal FM.
∗1
The above parameters can be set when
Pr. 160 User group read selection
= "0".
∗2
The parameter number in parentheses is the one for use with the operation panel (PA02) for the FR-E500 series or parameter unit (FR-PU04/FR-PU07).
∗3
The above parameters allow their settings to be changed during operation in any operation mode even if "0" (initial value) is set in
Pr. 77 Parameter write
selection
.
REMARKS
When calibrating a monitor output signal, which cannot be adjusted to 100% value without an actual load and a measurement
equipment, set
Pr. 54
to "21" (reference voltage output). 1440 pulses/s are output from the terminal FM.
The wiring length of the terminal FM should be 200m maximum.
NOTE
The initial value of the
calibration parameter C0 (Pr. 900)
is set to 1mA full-scale and 1440 pulses/s FM output frequency
at 60Hz. The maximum pulse train output of terminal FM is 2400 pulses/s.
When a frequency meter is connected to across terminals FM-SD to monitor the running frequency, the terminal FM
output is filled to capacity at the initial value if the maximum output frequency reaches or exceeds 100Hz. In this
case, the
Pr. 55
setting must be changed to the maximum frequency.
8VDC
T2
T1
Pulse width T1: Adjust using calibration parameter C0
Pulse cycle T2: Set with
Pr. 55
(frequency monitor)
Set with
Pr. 56
(current monitor)
(Digital indicator)
(-)
1440 pulses/s(+)
FM
SD
Indicator
1mA full-scale
analog meter
(-)
(+)
1mA
FM
SD
Calibration
resistor *1
Содержание FR-E710W-0.1K
Страница 49: ...40 MEMO ...
Страница 65: ...56 MEMO ...
Страница 288: ...288 MEMO ...
Страница 310: ...310 MEMO ...
Страница 334: ...334 MEMO ...
Страница 335: ...335 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 348: ...4 4 BCN C22005 679 MEMO BCN C22005 679 fm 4 ページ 2014年11月7日 金曜日 午前11時58分 ...