Parameter list with instruction codes
Appendix
A - 16
A.4
Parameter list with instruction codes
In the initial setting status, simple mode parameters and extended parameters can be displayed. Set
Pr. 160 "User group read selection" as required. So check the setting of Pr. 160 if parameters are not
shown or change the setting of Pr. 160 to lock parameters.
Parameter
Name
Initial
Value
Setting
Range
Remarks
160
User group read
selection
0
9999
Only the simple mode parameters can be displayed.
0
Simple mode and extended mode parameters can be
displayed.
1
Only parameters registered in the user group can be
displayed.
Tab. A-4:
Settings of parameter 160
NOTES
The parameters marked
are the simple mode parameters.
The parameters marked with
in the table allow its setting to be changed during opera-
tion even if "0" (initial value) is set in Pr. 77 "Parameter write selection".
Parameters for the option are displayed only when the option unit is installed.
The instruction codes (hexadecimal) for "read" and "write" on the right of the parameter number
are those used to set the parameter via communication. "Extended" indicates the setting of the
extended link parameter. (Refer to section 6.19 for communication.) The data code is contained in
the table columns to the right next to the parameter number.
The symbols in the table have the following meanings:
✔
: Setting the parameter is possible for this operation mode.
—: Setting the parameter is impossible for this operation mode.
Function
Parame-
ter
Instruction Code
Name
Control Mode-based Correspondence Table
Refer to
Page
Customer
Setting
Read
W
rit
e
Ext
ended
V/F control
General-pur-
pose magnetic
flux vector
control
Advanced
magnetic flux
vector control
Basic functions
0
00
80
0
Torque boost
✔
—
—
1
01
81
0
Maximum frequency
✔
✔
✔
2
02
82
0
Minimum frequency
✔
✔
✔
3
03
83
0
Base frequency
✔
—
—
4
04
84
0
Multi-speed setting
RH
✔
✔
✔
5
05
85
0
RM
✔
✔
✔
6
06
86
0
RL
✔
✔
✔
7
07
87
0
Acceleration time
✔
✔
✔
8
08
88
0
Deceleration time
✔
✔
✔
9
09
89
0
Electronic thermal O/L relay
✔
✔
✔
DC injection brake
10
0A
8A
0
DC injection brake operation
Fre-
quency
✔
✔
✔
11
0B
8B
0
Time
✔
✔
✔
12
0C
8C
0
Voltage
✔
✔
✔
—
13
0D
8D
0
Starting frequency
✔
✔
✔
Tab. A-5:
Parameter list with instruction codes (1)
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......