CC-Link IE Field Network Basic
Parameter
6 - 364
6.24.1 Programming
examples
This section provides programming examples which control the inverter with sequence programs.
●
System configuration example (when the MELSEC iQ-R series programmable controller is used)
●
Network parameter setting of the master station
Item
Program example
Refer to
page
Reading the inverter status
Reading the inverter status from the buffer memory of the master station
Setting the operation mode
Selecting the network operation mode
Setting the operation commands
Commanding the forward rotation and middle speed signals
Setting the monitoring function
Monitoring the output frequency
Reading a parameter value
Reading the value of Pr. 7 "Acceleration time"
Writing a parameter value
Setting "3.0 s" in Pr. 7 "Acceleration time"
Setting the running frequency
(running speed)
Setting to 50.00 Hz
Reading the fault records
Reading the inverter faults
Inverter reset
Perform inverter reset at an inverter alarm occurrence
I003125E
Fig. 6-174:
CC-Link IE Field Network Basic with programmable controller and two inverters
Item
Setting conditions
Start I/O No.
0000
Type
Master
All connect count
2
Remote input (RX)
X1000
Remote output (RY)
Y1000
Remote register (RWr)
W0
Remote register (RWw)
W100
Retry count
3
Tab. 6-163:
Network parameter of the master station
Power supply
R61P
Programmable
controller
CPU
R04CPU
Input module
RX40C7
(X20 to X2F)
Output module
RY40PT5P
(Y30 to Y3F)
Inverter
(Station No. 1)
Pr. 544 = 0
Pr. 544 = 0
Inverter
(Station No. 2)
Hub
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......