Parameter
CC-Link IE Field Network Basic
FR-E700 SC EC/ENE
6 - 369
Parameter reading
The following program reads Pr. 7 "Acceleration time" of station 1 inverter to D1.
●
Pr. 7 "Acceleration time" reading instruction code: H07 (hexadecimal)
●
For information about the instruction codes refer to the parameter list on page A-16.
●
The reply code at the time of instruction code execution is set to D2.
(For information about the reply code (RWr2) refer to page 6-360.)
I003134E
Fig. 6-181:
Program example 5
NOTE
For parameters having numbers 100 and later, change their link parameter extended settings (set
them to other than H00). Refer to page A-16 for details.
(0)
SM1536
SD1536.0
SD1540.0
M0
(4)
M0
X20
PLS
M300
(8)
M300
SET
M301
(10)
M301
X100F
MOV
H7
W102
SET
Y100F
RST
M301
SET
M302
(17)
M302
X100F
MOV
W3
D1
MOV
W2
D2
RST
Y100F
RST
M302
(25)
END
Check the data link status of the station 1
Read acceleration time (RWr3) and reply code
(RWr2) to D1 and D2 when the instruction code
execution completion (RX0F) turns on.
Write Pr. 7 read code (H07) to RWw2.
Turn off the instruction code execution request
(RY0F)
Turn on the instruction code execution request
(RY0F)
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......