CC-Link IE Field Network Basic
Parameter
6 - 370
Parameter writing
The following program changes the setting of Pr. 7 "Acceleration time" of station 1 inverter to 3.0 s.
●
Acceleration time writing instruction code: H87 (hexadecimal)
●
Acceleration time set data: K30 (decimal)
For information about the instruction codes refer to the parameter list on page A-16.
The reply code at the time of instruction code execution is set to D2.
(For information about the reply code (RWr2) refer to page 6-360.)
I003135E
Fig. 6-182:
Program example 6
NOTES
For parameters having numbers 100 and later, change their link parameter extended settings (set
them to other than H00). Refer to page A-16 for details.
For other functions, refer to the instruction codes on page 6-361.
(0)
SM1536
SD1536.0
SD1540.0
M0
(4)
M0
X20
PLS
M300
(8)
M300
SET
M301
(10)
M301
X100F
MOV
H87
W102
MOV
K30
W103
SET
Y100F
RST
M301
SET
M302
(19)
M302
X100F
MOV
W2
D2
RST
Y100F
RST
M302
(25)
END
Check the data link status of the station 1
Read reply code (RWr2) to D2 when the instruction
code execution completion (RX0F) turns on.
Write Pr.7 write (H87) to RWw2 and acceleration
time setting data (K30) to RWw3.
Turn off the instruction code execution request
(RY0F)
Turn on the instruction code execution request
(RY0F)
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......