Selection of operation mode and operation location
Parameter
6 - 172
6.17
Selection of operation mode and operation location
6.17.1
Operation mode selection (Pr. 79)
Used to select the operation mode of the inverter.
Mode can be changed as desired between operation using external command signals (external
operation), operation from the operation panel and PU (FR-PU07/FR-PU04) (PU operation),
combined operation of PU operation and external operation (external/PU combined operation),
and network operation (when RS485 communication is used).
The above parameter can be changed during a stop in any operation mode.
The priorities of the frequency commands when Pr. 79 = "3" are "Multi-speed operation (RL/
RM/RH/REX) > PID control (X14) > terminal 4 analog input (AU) > digital input from the
operation panel".
Purpose
Parameters that must be set
Refer to
Section
Operation mode selection
Operation mode selection
Pr. 79
Started in network operation mode
Operation mode at power on
Pr. 79, Pr. 340
Selection of control source
Selection of control source, speed com-
mand source and control location during
communication operation
Pr. 338, Pr. 339,
Pr. 551
Pr.
No.
Name
Initial
Value
Setting
Range
Description
Parameters referred to
Refer to
Section
79
Operation mode
selection
0
0
External/PU switchover mode
External operation mode at power on
15
4–6
24–27
232–239
75
161
178–182
190/192/
197
340
Jog frequency
Multi-speed
operation
Reset selection/
disconnected PU
detection/
PU stop selection
Frequency setting/
key lock operation
selection
Input terminal func-
tion selection
Output terminal
function selection
Communication
start-up mode
selection
1
Fixed to PU operation mode
2
Fixed to external operation mode
Operation can be performed by switching
between external and NET operation
mode
3
Combined operation mode 1
Running frequency:
Operation panel, and PU (FR-PU04/
FR-PU07) setting or external signal input
[multi-speed setting, across terminals
4-5 (valid when AU signal turns on)]
Start signal:
External signal input (terminal STF, STR)
4
External/PU combined operation mode 2
Running frequency:
External signal input (terminal 2, 4, JOG,
multi-speed setting, etc.)
Start signal:
Enter from the RUN key of the operation
panel and the FWD/REV keys of the PU
(FR-PU04/FR-PU07)
6
Switchover mode
Switchover between PU operation, exter-
nal operation, and NET operation is avail-
able while keeping the same operation
status.
7
External operation mode (PU operation
interlock)
X12 signal ON:
Operation mode can be shifted to PU
operation mode (output stop during
external operation)
X12 signal OFF:
Operation mode can not be switched to
PU operation mode.
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......