Selection of operation mode and operation location
Parameter
6 - 184
6.17.2
Operation mode at power on (Pr. 79, Pr. 340)
When power is switched on or when power comes back on after instantaneous power failure, the
inverter can be started up in network operation mode.
After the inverter has started up in the network operation mode, parameter write and operation
can be performed from a program.
Set this mode for communication operation using the inverter RS485 terminals.
The above parameters can be changed during a stop in any operation mode.
The above parameter can be set when Pr. 160 = 0.
Pr.
No.
Name
Initial
Value
Setting
Range
Description
Parameters referred to
Refer to
Section
79
Operation mode
selection
0
0–4/6/7
Select the operation mode.
(Refer to page 6-175)
79
Operation mode
selection
340
Communication
start-up mode
selection
0
0
As set in Pr. 79.
1
Started in network operation mode.
10
Started in network operation mode.
Operation mode can be changed between
the PU operation mode and network
operation mode from the operation
panel.
Содержание FR-D720S SC EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the case Product checking and part identification 1 4 ...
Страница 108: ...Operation panel Operation 4 20 ...
Страница 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Страница 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Страница 504: ...Specification change Appendix A 20 ...
Страница 505: ......
Страница 506: ......
Страница 510: ...Index Appendix A 24 ...
Страница 511: ......