4.19.4 Current average value monitor signal (Pr. 555 to Pr. 557)
The pulse output of the Current average monitor (Y93) signal is shown above.
For the terminal used for the Y93 signal output, assign the function by setting "93" (positive logic) or "193" (negative logic)
to
Pr. 190 RUN terminal function selection
. The function cannot be assigned to
Pr. 192 A,B,C terminal function selection
.
1) Setting of
Pr. 556 Data output mask time
The output current is unstable (transient state) right after the operation is changed from the acceleration/deceleration state
to the constant speed operation. Set the time for not obtaining (mask) transient state data in
Pr. 556
.
2) Setting of
Pr. 555 Current average time
The average output current is calculated during Hi output of start pulse (1s). Set the time taken to average the current
during start pulse output in
Pr. 555
.
The average value of the output current during
constant speed operation and the maintenance timer
value are output as a pulse to the Current average
monitor (Y93) signal.
The pulse width output to the I/O module of the
programmable controller or the like can be used as a
guideline to know abrasion of machines, elongation of
belt and the maintenance time for aged deterioration
of devices.
The Current average monitor (Y93) signal is output as
pulse for 20s as 1 cycle and repeatedly output during
constant speed operation.
Parameter
Number
Name
Initial Value
Setting Range
Description
555
Current average time
1s
0.1 to 1s
Time taken to average the current during start pulse
output (1s).
556
Data output mask time
0s
0 to 20s
Time for not obtaining (mask) transient state data.
557
Current average value
monitor signal output
reference current
Rated motor
current
0 to 500A
Reference (100%) for outputting the signal of the
current average value.
The above parameters can be set when
Pr. 160 Extended function display selection
= "0".
The above parameters allow their settings to be changed during operation in any operation mode even if "0" (initial value) is set in
Pr. 77 Parameter write selection
.
Refer to page 288
for the rated motor current.
Programmable controller
Output unit
Input unit
Maintenance
time
Parts have
reached their life
Drive unit
Output current average value (A)
1) Data output mask time
When the speed has changed to
constant from acceleration/deceleration,
Y93 signal is not output for
Pr. 556
time.
2) Start pulse
Output as Hi pulse shape for 1s (fixed)
Output current set in
Pr. 555
time is averaged
3) Output current average value pulse
The averaged current value is output for 0.5 to 9s
(10 to 180%) during start pulse output.
Signal output time =
Pr. 557
(A)
4) Maintenance timer pulse
The maintenance timer value (
Pr. 503
) is
output as Hi pulse shape for 2 to 9s
(16000h to 72000h)
Signal output time =
40000h
5) End pulse
Output as low pulse
shape for 1 to 16.5s
Time
Y93 signal
1 cycle (20s)
Next cycle
Rotation speed
From acceleration to constant speed operation
Pr. 503
100h
5s
5s