Monitor display and monitor output signal
Speed setting to output terminal status on the PU main monitor are selected by "other monitor selection" of the parameter unit (FR-PU07).
The cumulative energization time and actual operation time are accumulated from 0 to 65535 hours, then cleared, and accumulated again from 0.
When the operation panel is used, the time is displayed up to 65.53 (65530h) in the indication of 1h = 0.001, and thereafter, it is added up from 0.
Actual operation time is not accumulated when the cumulative operation time is less than 1h until turning OFF of the power supply.
When using the parameter unit (FR-PU07), "kW" is displayed.
Since the panel display of the operation panel is 4 digits in length, the monitor value of more than "9999" is displayed as "----".
The monitored values are retained even if a drive unit fault occurs. Resetting will clear the retained values.
The motor load factor is displayed as 0% in the low-speed range lower than 10% of the rated motor speed.
The set speed displayed indicates the speed to be output when the start
command is ON. Different from the speed setting displayed when
Pr. 52
= "5", the
value based on maximum/minimum setting and speed jump is displayed.
REMARKS
By setting "0" in
Pr. 52
, the monitoring of output speed to fault display can be selected in sequence by
.
When the operation panel is used, the displayed units are Hz and A only, and the others are not displayed.
The monitor set in
Pr. 52
is displayed in the third monitor position. However, change the output current monitor for the motor
load factor.
The monitor displayed at power-ON is the first monitor. Display the monitor you want to display on the first monitor and hold
down
for 1s. (To return to the rotation speed monitor, hold down
for 1s after displaying the rotation speed monitor.)
Example)When
Pr. 52
is set to "20" (cumulative energization time), the monitor is displayed on the operation panel as described
below.
(2) Display set speed during stop
(Pr. 52)
When "100" is set in
Pr. 52
, the set speed and
rotation speed are displayed during stop and
operation respectively.
Pr. 52
0
100
During
running/stop
During stop
During
running
Rotation speed
Rotation speed
Set speed
Rotation speed
Output current
Output current
Output voltage
Output voltage
Fault display
Fault display
REMARKS
During an error, the rotation speed at error occurrence appears.
During MRS signal is ON, the values displayed are the same as during a stop.
Initial Value
With fault
Output current monitor
Output voltage monitor
Rotation speed monitor
Power-on monitor (first monitor)
Second monitor
Third monitor
Fault monitor
With fault
Output current monitor
Output voltage monitor
Rotation speed monitor
Power-on monitor (first monitor)
Second monitor
Third monitor
Fault monitor
With fault
Output current monitor
Cumulative energization time monitor
Rotation speed monitor
Power-on monitor (first monitor)
Second monitor
Third monitor
Fault monitor