132
Monitor display and monitor output signal
4.12 Monitor display and monitor output signal
4.12.1 Speed display and speed setting (Pr. 37, Pr. 144, Pr. 505)
The above parameter can be set when
Pr. 160 Extended function display selection
= "0".
The maximum value of the setting range differs according to the
Pr. 1 Maximum setting
,
and it can be calculated from the following formula.
Note that the maximum setting value of
Pr. 37
is 9998 if the result of the above formula exceeds 9998.
The value left of the slash is for the 2.2K drive unit or lower. The one right of the slash is for the 3.7K drive unit.
To display a machine speed, set
Pr. 37
to the machine speed at the frequency set in
Pr. 505
, and set
Pr. 144
to the number of
motor poles (4, 6).
For example, when
Pr. 505
= "100Hz" and
Pr. 37
= "1000", "1000" is displayed on the set frequency monitor when the
running frequency is 100Hz. When running frequency is 50Hz, "500" is displayed.
When the number of motor poles +100 is set in
Pr. 144
, values are displayed in motor speed increments. (When
Pr. 37
= "0")
To change the display increments to frequency, set the number of motor poles in
Pr. 144
. (When
Pr. 37
= "0")
A combination of the
Pr. 37
and
Pr. 144
settings determines the monitored item and the setting increment as shown in the
table below. (Initial settings are outlined with bold borders)
Purpose
Parameter that should be Set
Refer to
Page
Display motor speed
Set speed
Speed display and speed setting
Pr. 37, Pr. 144, Pr. 505
Change PU monitor display data
Monitor display/PU main display
data selection
Cumulative monitor clear
Pr. 52, Pr. 54, Pr. 170, Pr. 171,
Pr. 268, Pr. 563, Pr. 564, Pr. 891
Change the monitor output from
terminal FM
Terminal FM function selection
Pr. 54
Set the reference of the monitor
output from terminal FM
Terminal FM standard setting
Pr. 55, Pr. 56
Adjust terminal FM outputs
Terminal FM calibration
Pr. 900
The increments of the motor speed and the monitored items displayed on the operation panel and PU (FR-PU07) can
be switched among frequency, machine speed, etc.
Parameter
Number
Name
Initial
Value
Setting Range
Description
37
Speed display
0
0
Speed display, setting
0.01 to 9998
Machine speed at
Pr. 505
.
144
Speed setting switchover
104/106
2, 4, 6, 8, 10, 102,
104, 106, 108, 110
Set the number of motor poles when displaying the
frequency.
505
Speed setting reference
100Hz/
1 to 200Hz
Set the reference speed for
Pr. 37
.
Maximum setting value of
Pr. 37
<
16777.215
Pr. 505
setting
Setting value of
Pr. 1
(Hz)
Pr. 37
Setting
Pr. 144
Setting
Output Frequency
Monitor
Set Frequency
Monitor
Running Speed
Monitor
Parameter Setting
0
(initial value)
2 to 10
0.01 Hz
0.01 Hz
0.01 Hz
0.01 Hz
102 to 110
1 r/min
1 r/min
*
1 r/min
1 r/min
0.01 to 9998
2 to 10
0.001 (Machine speed
*
0.001 (Machine speed
0.001 (Machine speed
*
0.01 Hz
102 to 110
0.01 Hz
0.01 Hz
0.01 Hz
0.01 Hz
* Motor speed r/min conversion formula....... frequency
120/number of motor poles (
Pr. 144
)
Machine speed conversion formula
............. Pr. 37
frequency/
Pr. 505
setting (Hz)
For
Pr. 144
in the above formula, the value is "
Pr. 144
-100" when "102 to 110" is set in
Pr. 144
.
Pr. 505
is always set as frequency (Hz).
Содержание FR-D720-0.2K-G
Страница 45: ...34 MEMO ...
Страница 293: ...290 MEMO ...
Страница 294: ...291 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...