PARAMETER LIST
162
Automatic restart after
instantaneous power failure
selection
0, 1, 10, 11
1
165
Stall prevention operation level
for restart
0 to 200%
150%
166
Output current detection signal
retention time
0 to 10s,
9999
0.1s
167
Output current detection
operation selection
0, 1
0
168
Parameter for manufacturer setting. Do not set.
169
170
Watt-hour meter clear
0, 10, 9999
9999
171
Operation hour meter clear
0, 9999
9999
178
STF terminal function selection
0 to 5, 7, 8,
10, 12, 14,
16, 18, 24,
25, 37, 60,
62, 65 to 67,
9999
60
179
STR terminal function
selection
0 to 5, 7, 8,
10, 12, 14,
16, 18, 24,
25, 37, 61,
62, 65 to 67,
9999
61
180
RL terminal function selection 0 to 5, 7, 8,
10, 12, 14,
16, 18, 24,
25, 37, 62,
65 to 67,
9999
0
181
RM terminal function selection
1
182
RH terminal function selection
2
190
RUN terminal function
selection
0, 1, 3, 4, 7,
8, 11 to 16,
25, 26, 46,
47, 64, 70,
90, 91, 93,
95, 96, 98,
99, 100, 101,
103, 104,
107, 108, 111
to 116, 125,
126, 146,
147, 164,
170, 190,
191, 193,
195, 196,
198, 199,
9999
0
Parameter
Name
Setting
Range
Initial
Value
192
A,B,C terminal function
selection
0, 1, 3, 4, 7,
8, 11 to 16,
25, 26, 46,
47, 64, 70,
90, 91, 95,
96, 98, 99,
100, 101,
103, 104,
107, 108, 111
to 116, 125,
126, 146,
147, 164,
170, 190,
191, 195,
196, 198,
199, 9999
99
232
Multi-speed setting (speed 8)
0 to 400Hz,
9999
9999
233
Multi-speed setting (speed 9)
0 to 400Hz,
9999
9999
234
Multi-speed setting (speed 10)
0 to 400Hz,
9999
9999
235
Multi-speed setting (speed 11)
0 to 400Hz,
9999
9999
236
Multi-speed setting (speed 12)
0 to 400Hz,
9999
9999
237
Multi-speed setting (speed 13)
0 to 400Hz,
9999
9999
238
Multi-speed setting (speed 14)
0 to 400Hz,
9999
9999
239
Multi-speed setting (speed 15)
0 to 400Hz,
9999
9999
240
Soft-PWM operation selection 0, 1
1
241
Analog input display unit
switchover
0, 1
0
244
Cooling fan operation selection 0, 1
1
245
Rated slip
0 to 50%,
9999
9999
246
Slip compensation time
constant
0.01 to 10s
0.5s
247
Constant-power range slip
compensation selection
0, 9999
9999
249
Earth (ground) fault detection
at start
0, 1
1
250
Stop selection
0 to 100s,
1000 to
1100s, 8888,
9999
9999
251
Output phase loss protection
selection
0, 1
1
255
Life alarm status display
(0 to 15)
0
256
Inrush current limit circuit life
display
(0 to 100%)
100%
257
Control circuit capacitor life
display
(0 to 100%)
100%
258
Main circuit capacitor life
display
(0 to 100%)
100%
259
Main circuit capacitor life
measuring
0, 1 (2, 3, 8,
9)
0
Parameter
Name
Setting
Range
Initial
Value